Operation and Maintenance Manual for Rosenberg
Compact Ventilation Appliance series SupraBox
Comfort
BA 112 BB 11/12/A/SupraBox 1
16
Only the connections for the ventilation ducts, condensate and water must properly installed on site.
Furthermore the electrical supply as well as external sensors or optional accessories such as duct
heaters etc. must be connected.
The remote operator control must be connected to the control system using the provided cable and
placed at the ventilation system or nearby. The electrical connection has to be made according to the
wiring diagram, see the additional operating manual control for the control system.
5.3 Connection of the ventilation ducts to the unit
The connection sleeves of the Rosenberg-SupraBox Comfort are provided as circular
tube spigots, with T-sealing lip sizes as shown in the unit drawings. The duct system
must be installed according to the valid technical standards and regulations and must
support the dead load by installations of the customer. Additional requirements
concerning sound insulation separate vibration isolation can be provided as elastic
connections. These are not standard in the scope of delivery, but offered as
accessories. The fresh air and exhaust air duct must be isolated against condensate water.
5.4 Electric Installation
Only a professional electrician may install the electrical connection according to the
VDE-regulations. The connection must properly be made according to the wiring
diagram and the configuration scheme.
All screw joints must be checked before Setup and retightened if necessary. Further
installation instructions can be found on the separate manual of the control.
5.5 Connection of the condensate, exhaust air and overflow pipes
The Suprabox is equipped with maintenance and condensate pan. As you can see in the device
overview, the maintenance pan is situated in the fresh air and the condensate pan in the exhaust air.
Both pans have a flexible tube at the bottom side of the unit with an inner diameter of 19.4 mm. Do
never remove them and check the correct seating before the unit is assembled.
The exhaust air pipe of the maintenance pan is only used for cleaning. Therefore it is necessary to
seal the tube of the maintenance pan by appropriate material (e.g. tape) in order to avoid a volume
flow leakage in this area.
Especially in the cold seasons there could be condensate in the exhaust air duct of the reverse flow
heat exchanger. In order to make sure the condensate drains correctly via the condensate pan and to
avoid air leakage, it is important to attach a vacuum trap as shown in the drawing below. Alternatively
a hose can be fixed at the unit to replace a trap. The minimum sizes must be observed by the
customer. Fill the trap with water before startup. Protect the trap against desiccation and in cold