Electronics Trim of an 8712D, 8732C, or 8742C
Magnetic Flowmeter Transmitter
The Rosemount 8714D is a high-precision instrument that supplies a 8712D, 8732C, or
8742C Magnetic Flowmeter Transmitter with a voltage corresponding exactly to 0.00 ft/s,
3.00 ft/s, 10.00 ft/s, and 30.00 ft/s. The precise 30.00 ft/s voltage signal may be used to
recalibrate or verify operation of the transmitter. (This same procedure is used by the factory
to calibrate the transmitter; it is rarely needed by customers.)
Perform this procedure only if you believe that transmitter is no longer accurate.
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount
®
8714D. It does not
provide instructions for detailed configuration, diagnostics, maintenance, service,
troubleshooting. The manual and this QIG are also available electronically on
www.rosemount.com.
WARNING
Explosions could result in death or serious injury:
In an Explosion-proof/Flame-proof installation, do not remove the transmitter covers
when power is applied to the unit.
Electrical shock can result in death or serious injury
• Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN USA
55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Emerson Process Management
Flow
Groeneveldselaan 6-8
3903 AZ Veenendaal
The Netherlands
T 31 (0) 318 549 549
F 31 (0) 318 549 559
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
4764_revBA_QIG.fm Page 2 Tuesday, June 22, 2004 1:49 PM