Quick Install Guide

00825-0100-4727, Rev DC

November 2017

Rosemount

®

 8700 Magnetic Flowmeter

Sensor

Содержание 8712E

Страница 1: ...Quick Install Guide 00825 0100 4727 Rev DC November 2017 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 2: ...nnect and seal them Appropriate care should be taken to prevent water ingress The sensor should be supported by the pipeline Pipe supports are recommended on both the inlet and outlet sides of the sensor pipeline There should be no additional support attached to the sensor Use proper PPE Personal Protection Equipment including safety glasses and steel toed shoes Do not lift the meter by holding th...

Страница 3: ...th a lifting sling on each side of the housing Standard pressure 3 in through 36 in flanged magnetic flowmeters come with lifting lugs High pressure above 600 1 in through 24 in flanged magnetic flowmeters come with lifting lugs Wafers and sanitary magnetic flowmeters do not come with lifting lugs Example lifting without and with lifting lugs Figure 1 1 A Without lifting lugs B With lifting lugs N...

Страница 4: ...63 8732E Magnetic Flowmeter System with PROFIBUS PA digital fieldbus 00825 0100 4665 8712E Magnetic Flowmeter System 00825 0100 4664 8712H Magnetic Flowmeter Systems 00825 0100 4729 For additional installation information configuration maintenance and troubleshooting refer to the appropriate reference manual All user documentation can be found at www emerson com For more contact information see Se...

Страница 5: ...e 0800 917 901 India 800 440 1468 Argentina 54 11 4837 7000 Germany 0800 182 5347 Pakistan 888 550 2682 Brazil 55 15 3413 8000 Italy 8008 77334 China 86 21 2892 9000 Venezuela 58 26 1731 3446 Central East ern 41 0 41 7686 111 Japan 81 3 5769 6803 Russia CIS 7 495 981 9811 South Korea 82 2 3438 4600 Egypt 0800 000 0015 Singapore 65 6 777 8211 Oman 800 70101 Thailand 001 800 441 6426 Qatar 431 0044 ...

Страница 6: ...acy over widely varying process conditions install the sensor with a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane Upstream and downstream straight pipe diameters Figure 3 1 A Five pipe diameters upstream B Two pipe diameters downstream C Flow direction Installations with reduced upstream and downstream straight runs are possible In red...

Страница 7: ...Flow direction arrow Figure 3 2 November 2017 Quick Install Guide Quick Install Guide 7 ...

Страница 8: ...led orientation must also be considered Vertical installation with upward process fluid flow keeps the cross sectional area full regardless of flow rate Horizontal installation should be restricted to low piping sections that are normally full Sensor orientation Figure 3 3 A Flow direction Quick Install Guide November 2017 8 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 9: ...ng orientation that positions the top of the sensor at 90 degrees from the vertical position as shown on the right of the Electrode Orientation figure Electrode orientation Figure 3 4 A Correct orientation B Incorrect orientation The sensor may require a specific orientation to comply with Hazardous Area T code rating Refer to the approrpirate reference manual for any potential restrictions Novemb...

Страница 10: ...de require only one gasket on each process connection Note Metallic or spiral wound gaskets should not be used as they will damage the liner face of the sensor If spiral wound or metallic gaskets are required for the application lining protectors must be used Gasket placement for flanged sensors Figure 4 1 A Grounding ring and gasket optional B Customer supplied gasket Bolts Note Do not bolt one s...

Страница 11: ...e bolts tighten the bolts in a similar crosswise sequence Repeat this entire tightening sequence at 40 60 80 and 100 of the suggested torque values If leakage occurs at the suggested torque values the bolts can be tightened in additional 10 increments until the joint stops leaking or until the measured torque value reaches the maximum torque value of the bolts Practical consideration for the integ...

Страница 12: ...lass 300 pound feet 005 0 5 in 15 mm 8 8 N A N A 010 1 in 25 mm 8 12 6 10 015 1 5 in 40 mm 13 25 7 18 020 2 in 50 mm 19 17 14 11 025 2 5 in 65 mm 22 24 17 16 030 3 in 80 mm 34 35 23 23 040 4 in 100 mm 26 50 17 32 050 5 in 125 mm 36 60 25 35 060 6 in 150 mm 45 50 30 37 080 8 in 200 mm 60 82 42 55 100 10 in 250 mm 55 80 40 70 120 12 in 300 mm 65 125 55 105 140 14 in 350 mm 85 110 70 95 160 16 in 400...

Страница 13: ...400 mm 220 280 410 610 180 18 in 450 mm 190 340 330 420 200 20 in 500 mm 230 380 440 520 240 24 in 600 mm 290 570 590 850 Suggested flange bolt torque values for Rosemount 8705 sensors with non fluoropolymer liners EN 1092 1 Table 4 4 Size Code Line Size Non fluoropolymer liners in Newton meters PN 10 PN 16 PN 25 PN 40 005 0 5 in 15 mm N A N A N A 20 010 1 in 25 mm N A N A N A 30 015 1 5 in 40 mm ...

Страница 14: ...ents that must be met Wafer sensors installation components and assembly requirements Figure 4 3 A Ground ring optional B Customer supplied gaskets C Spacer installation horizontal meters D Spacer installation vertical meters E O ring F Installation studs nuts and washers optional G Wafer alignment spacer H Flow Gaskets The sensor requires a gasket at each process connection The gasket material se...

Страница 15: ...1 5 40 JIS 10K 20K 0A20 2 50 JIS 10K 20K 0A30 3 80 JIS 10K 0B15 1 5 40 JIS 40K AA15 1 5 40 ASME 150 AA20 2 50 ASME 150 AA30 3 80 ASME 150 AA40 4 100 ASME 150 AA60 6 150 ASME 150 AA80 8 200 ASME 150 AB15 1 5 40 ASME 300 AB20 2 50 ASME 300 AB30 3 80 ASME 300 AB40 4 100 ASME 300 AB60 6 150 ASME 300 AB80 8 200 ASME 300 DB40 4 100 EN 1092 1 PN10 16 DB60 6 150 EN 1092 1 PN10 16 DB80 8 200 EN 1092 1 PN10...

Страница 16: ...s check for leaks at the flanges after tightening the flange bolts All sensors require a second tightening 24 hours after initial flange bolt tightening Stud specifications Table 4 6 Nominal sensor size Stud specifications 0 15 1 in 4 25 mm 316 SST ASTM A193 Grade B8M Class 1 threa ded mounted studs 1 8 in 40 200 mm CS ASTM A193 Grade B7 threaded mounting studs Flange bolt torquing sequence Figure...

Страница 17: ...y be damaged Rosemount 8711 torque specifications Table 4 7 Size code Line size Pound feet Newton meter 015 1 5 in 40 mm 15 20 020 2 in 50 mm 25 34 030 3 in 80 mm 40 54 040 4 in 100 mm 30 41 060 6 in 150 mm 50 68 080 8 in 200 mm 70 95 4 3 Sanitary senors Gaskets The sensor requires a gasket at each of its connections to adjacent devices or piping The gasket material selected must be compatible wit...

Страница 18: ...Sanitary sensor gasket and clamp alignment Figure 4 5 A User supplied clamp B User supplied gasket Quick Install Guide November 2017 18 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 19: ...5 1 Type of pipe Grounding straps Grounding rings Reference elec trode Lining protec tors Conductive un lined pipe See Figure 5 1 See Figure 5 2 See Figure 5 4 See Figure 5 2 Conductive lined pipe Insufficient grounding See Figure 5 2 See Figure 5 1 See Figure 5 2 Non conductive pipe Insufficient grounding See Figure 5 3 Not recommen ded See Figure 5 3 Note For line sizes 10 inch and larger the gr...

Страница 20: ...tive pipe Figure 5 2 A Grounding rings or lining protectors Grounding with grounding rings or lining protectors in non conductive pipe Figure 5 3 A Grounding rings or lining protectors Quick Install Guide November 2017 20 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 21: ...Grounding with reference electrode in conductive unlined pipe Figure 5 4 Grounding for line sizes 10 in and larger Figure 5 5 November 2017 Quick Install Guide Quick Install Guide 21 ...

Страница 22: ...6 Wiring sensor to transmitter Wiring 8732ES using component cable Figure 6 1 Quick Install Guide November 2017 22 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 23: ...Wiring 8732ES using combination cable Figure 6 2 November 2017 Quick Install Guide Quick Install Guide 23 ...

Страница 24: ...Wiring 8712ES using component cable Figure 6 3 Quick Install Guide November 2017 24 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 25: ...Wiring 8712ES using combination cable Figure 6 4 November 2017 Quick Install Guide Quick Install Guide 25 ...

Страница 26: ...Wiring 8732EM using component cable Figure 6 5 Quick Install Guide November 2017 26 Rosemount 8700 Magnetic Flowmeter Sensor ...

Страница 27: ...Wiring 8732EM using combination cable Figure 6 6 November 2017 Quick Install Guide Quick Install Guide 27 ...

Страница 28: ...Republic of Singapore T 65 6777 8211 F 65 6770 8003 Emerson Automation Solutions United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U K T 44 0870 240 1978 F 44 0800 966 181 Emerson Automation Solutions Japan 1 2 5 Higashi Shinagawa Shinagawa ku Tokyo 140 0002 Japan T 81 3 5769 6803 F 81 3 5769 6844 2017 Rosemount Inc All rights reserved The...