Reference Manual
00809-0100-4026, Rev FA
July 2009
7-27
Rosemount 5400 Series
Application Errors
When product surface is near
the tank bottom, the transmitter
enters alarm mode (see “Alarm
May be caused by reduction of projected
surface area close to sloping tank bottom.
Action:
• Increase parameter
Empty Tank
Detection Area
if measurement in this
region is not crucial, see “Empty Tank
Detection Area” on page C-4 and C-8
• Make sure that the
Bottom Echo
Visible
parameter is not set, see
“Bottom Echo Visible” on page C-4
Incorrect level.
Action:
• Check Tank Height configuration
• For rapid level changes, check the
Damping Value. (See “Damping
Incorrect level.
May be caused by wrong Range Value
settings.
Action:
• Check that the Upper Range Value
matches the 100 % level in the tank
Incorrect level when using a
pipe.
May be caused by an incorrectly
configured Pipe Inner Diameter.
Action:
• Check that the actual Pipe Inner
Diameter matches the configured
Inner Diameter
Alarm
Содержание 5401
Страница 2: ......
Страница 4: ......
Страница 10: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series TOC 6 ...
Страница 24: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 2 10 ...
Страница 80: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 5 26 ...
Страница 90: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 6 10 ...
Страница 160: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series B 16 ...
Страница 174: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series C 14 ...
Страница 177: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Index 3 Rosemount 5400 Series ...
Страница 178: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series Index 4 ...
Страница 179: ......