Reference Manual
00809-0100-4026, Rev FA
July 2009
Rosemount 5400 Series
C-8
Empty Tank Detection Area
If the signal from the product surface is lost within the region given by the
parameter
Empty Tank Detection Area
, the tank is considered empty and the
product level is presented as zero.
If the surface is lost above the Empty Tank Detection Area, the transmitter
starts searching the entire tank for the surface.
The Empty Tank Detection Area can be increased if the surface is lost outside
the
Empty Tank Detection Area
in a non-critical region of the tank.
1. Disable
Use Automatic Empty Tank Handling
Settings
.
2. Type the desired value in the
Empty Tank Detection Area
input field.
See “Empty Tank Detection Area” on page C-4 for further information.
Amplitude
D
ist
a
n
ce
If the product
surface is lost in this
region the tank is
considered empty.
Содержание 5401
Страница 2: ......
Страница 4: ......
Страница 10: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series TOC 6 ...
Страница 24: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 2 10 ...
Страница 80: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 5 26 ...
Страница 90: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 6 10 ...
Страница 160: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series B 16 ...
Страница 174: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series C 14 ...
Страница 177: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Index 3 Rosemount 5400 Series ...
Страница 178: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series Index 4 ...
Страница 179: ......