Quick Installation Guide
00825-0100-4716, Rev DA
October 2009
Rosemount 3095 MultiVariable
27
P
ATEX Dust
Certificate Number: KEMA02ATEX2321
II 1 D T90°C (-50°C
T
amb
80°C)
Vmax = 55 Vdc
Imax = 23 mA
IP66
1180
IECEx Certifications (Fieldbus)
4/Y
IECEx Intrinsic Safety
Certificate Number: IECEx BAS05.0023X
Ex ia IIC T4 (-45°C
T
a
70°C)
Ex ia IIC T5 (-45°C
T
a
40°C)
The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R)
of the load connected to the 4-pin connector must not exceed the following values:
Conditions of Certification (X):
When fitted with the transient option, the apparatus is not capable of withstanding the
500V electrical strength test as defined in Clause 6.4.12 of IEC 60079-11: 1999. This
must be taken into account during installation.
5
IECEx Type n
Certificate Number: IECEx BAS05.0024X
Ex nC IIC T4 (-45°C
T
a
70°C)
Ex nC IIC T5 (-45°C
T
a
40°C)
U
i
= 55V dc max
Conditions of Certification (X):
When fitted with the transient option, the apparatus is not capable of withstanding the
500V electrical strength test as defined in Clause 8 of IEC 60079-15: 1987. This must
be taken into account during installation.
Table 11. Input Parameters
Fieldbus I.S.
FISCO
U
i
= 30Vdc
U
i
= 17.5Vdc
I
i
= 300 mAdc
I
i
= 380 mAdc
P
i
= 1.3 W
P
i
= 5.32 W
C
i
= 3.3 nF
C
i
5 nF
L
i
= 0
L
i
10 mH
Table 12. RTD Terminals Entity Parameters
U
o
= 30Vdc
I
o
= 19 mAdc
P
o
= 140 mW
Group
Capacitance
(
F)
Inductance
(mH)
or L/R Ratio
H/Ohm
IIC
0.066
96
247
IIB
0.56
365
633
IIA
1.82
696
633
Содержание 3095MF Series
Страница 29: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 29 ...
Страница 30: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 30 ...
Страница 31: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 31 ...
Страница 32: ...Quick Installation Guide 00825 0100 4716 Rev DA October 2009 Rosemount 3095 MultiVariable 32 ...