
Figure 6-2: LOI Menu
Assign PV
HART Revision
6.3 Switch HART Revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the Rosemount 2051 will load a generic menu with limited
capability. The following procedures will switch the HART Revision mode from
the generic menu:
Procedure
Manual Setup > Device Information > Identification > Message
a) To change to HART Revision 5, Enter: HART5 in the Message field.
b) To change to HART Revision 7, Enter: HART7 in the Message field.
Note
See
Table 6-1
to change HART Revision when the correct device driver is
loaded.
Quick Start Guide
February 2019
22
Rosemount 2051 Pressure Transmitter Quick Start Guide