Table 6-1: Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key
Sequence
(continued)
Function
Fast Key Sequence
HART 7
HART 5
Descriptor
2, 2, 7, 1, 5
2, 2, 7, 1, 4
Digital to Analog Trim (4–
20 mA output)
3, 4, 2
3, 4, 2
Disable Configuration
Buttons
2, 2, 6, 3
2, 2, 6, 3
Rerange with Keypad
2, 2, 2, 1
2, 2, 2, 1
Loop Test
3, 5, 1
3, 5, 1
Lower Sensor Trim
3, 4, 1, 2
3, 4, 1, 2
Message
2, 2, 7, 1, 6
2, 2, 7, 1, 5
Scaled D/A Trim (4–20 mA
output)
3, 4, 2
3, 4, 2
Sensor Temperature/Trend 3, 3, 2
3, 3, 2
Upper Sensor Trim
3, 4, 1, 1
3, 4, 1, 1
Digital Zero Trim
3, 4, 1, 3
3, 4, 1, 3
Password
2, 2, 6, 5
2, 2, 6, 4
Scaled Variable
3, 2, 2
3, 2, 2
HART Revision 5 to HART
Revision 7 switch
2, 2, 5, 2, 3
2, 2, 5, 2, 3
Long Tag
(1)
2, 2, 7, 1, 2
N/A
Find Device
(1)
3, 4, 5
N/A
Simulate Digital Signal
(1)
3, 4, 5
N/A
(1)
Only available in HART Revision 7 mode.
6.2 Verifying configuration with LOI
The optional LOI can be used for commissioning the device. The LOI is a two-
button design with internal and external/rear buttons. On a polished stainless
steel housing, buttons are located internally both on the display and terminal
side of the transmitter. On an aluminum housing, buttons are located on the
display and externally underneath the top metal tag. To activate the LOI, push
any button. LOI button functionality is shown on the bottom corners of the
display. See
Table 6-2
and
Figure 6-2
for button operation and menu
information.
Quick Start Guide
February 2019
20