background image

11 

TF 200.01.0047_eng 

Basic 

(40-44012 and 40-44013) 
 

Construction 

The wall must be made of a material suited 
for screw mounting and approved for damp 
rooms.  
The hatched area is the minimum area for 
reinforcement of the wall. 
Reinforcement from floor to ceiling is 
advisable. 
Load-tested in Accordance to DS/ISO 17966, 
the maximum user weight has been fixed at 
400kg (881 lbs).  

 
Max. tensile load of upper screws  

85kg/screw (187 lbs) 
 
The washbasin is supplied with a set of 6 
screws and rawlplugs suitable for mounting 
on a concrete wall. The fitter should always 
consider the material, condition and strength 
of the wall and use screws and rawlplugs 
suitable for the specific wall type.  
 

Plumbing 

The drain is Ø32 

(1 ¼”) and ends in an 

Ø32x88.5° drain elbow. 
The maximum protrusion of drain connection 
and elbow from the wall is 90mm 

(3 ½”) to 

allow for the covers.   
The water supply ends in 2 (two) 90° shut-off 
valves with ½” outside thread pointing 
downward (not included). 
The maximum protrusion of the shut-off valves 
from the wall is 90mm 

(3 ½”) to allow for the 

covers. 
 
It is important that all hoses for water 
connection and drain are flexible to allow the 
frame to move freely within the height 
adjustment range of 710-1010mm 

(28” – 39 

8/10”) (including washbasin).  
 
If a location of water supply and drain different 
from the recommended positioning is required 
or if there is a floor drain, the Support Washbasin 
will have no covers.

 

 

For purchase of adapters for connection to 
various standard installations, see ”Connection 
Adapters 

– Other Washbasins”. 

 
 
Note 

The illustrations show the left-hand model 40-
44012 

 

Содержание 40-44010

Страница 1: ...Ropox Support Washbasin Fixed Basic Manual USER MANUAL MOUNTING INSTRUCTIONS Keep this manual with the product at all times TF 200 01 0047_eng Dato 29 08 2022 PA 2004 00634 ...

Страница 2: ...INTERFACES 10 4 2 CONNECTION ADAPTERS 13 4 3 LIST OF COMPONENTS 14 4 4 INSTALLATION OF PRODUCT 16 4 4 1 Support Washbasin Fixed 40 44010 11 16 4 4 2 Support Washbasin with Basic frame 40 4012 13 17 4 4 3 Mounting of covers for 40 44012 13 accessories 22 4 4 4 Support Washbasin with Manual frame 40 44014 15 26 4 4 5 Mounting of covers for 40 44014 15 34 5 PERFORMANCE TEST 38 6 SAFETY IN USE 38 7 SE...

Страница 3: ...understood before use Always keep this manual in close proximity of the product The use installation and service of this product must be in compliance with this manual to avoid accidents and serious personal injury Never use or handle this product in other ways specified in this manual as it can result in personal safety hazards and or cause damage to the product Persons installing and or using th...

Страница 4: ...ance Cleaning and user maintenance shall not be made by children without supervision Do not use the product if it has defects or have become damaged before being repaired or replaced If the control box makes unusual noise or smells switch off the mains voltage immediately Take care that the cables are not damaged Unplug the mains cable on mobile equipment before it is moved The products must only ...

Страница 5: ...gulation EU 2017 745 Council Directive 2006 42 EC on machinery Council Directive 2011 65 EU RoHS Manufacturer name and address Date of production Stock number Serial number Consult manual for important safety related information warnings and safety precautions Do not dispose as unsorted municipal waste Product must be returned to a designated recycling station Operating and storing temperatures ma...

Страница 6: ...nthetic marble composite Welded steel pipes St 37 aluminum Chrome Accessories 40 40935 40 44021 40 44022 40 44027 40 44028 40 44020 40 44033 40 44040 Plug with overflow Cover plates left for Fixed and Basic Cover plates right for Fixed and Basic Cover plates left for Manual Cover plates right for Manual Plumbing kit for Manual Plumbing kit for Fixed and Basic Mixer tap 3 2 Product description The ...

Страница 7: ...does not have essential performance as the patient and user do not experience any risk in case of loss of product function performance 3 6 Nonclinical functions Height adjusting offers better ergonomics to the user 3 7 Clinical functions The product does not have any clinical functions 3 8 Product dimensions Fixed 40 44001 11 Mixertap is accessory Basic height adjustment 40 44012 13 Mixertap is ac...

Страница 8: ...8 TF 200 01 0047_eng Manual height adjustment 40 44004 05 Mixertap is accessory Accessories covers 40 44021 22 633mm 1000mm 580mm 657mm 125mm 273mm 90mm 550 850mm 653mm ...

Страница 9: ...efore adjustment of these models Manual height adjustment applying to 40 44014 15 The height of the washbasin may be easily adjusted by means of the detachable hand crank Warning The product should always be able to travel the full range of actuation without colliding with objects Failing to do so will compromise the product stability and introduce risk of squeezing body parts Special care should ...

Страница 10: ...for the specific wall type Plumbing The drain is Ø32 1 and ends in an Ø32x88 5 drain elbow The maximum protrusion of drain connection and elbow from the wall is 90mm 3 to allow for the covers The water supply ends in 2 two 90 shut off valves with outside thread pointing downward not included The maximum protrusion of the shut off valves from the wall is 90mm 3 to allow for the covers If a location...

Страница 11: ...g The drain is Ø32 1 and ends in an Ø32x88 5 drain elbow The maximum protrusion of drain connection and elbow from the wall is 90mm 3 to allow for the covers The water supply ends in 2 two 90 shut off valves with outside thread pointing downward not included The maximum protrusion of the shut off valves from the wall is 90mm 3 to allow for the covers It is important that all hoses for water connec...

Страница 12: ...ype Plumbing The drain is Ø32 1 and ends in an Ø32x88 5 drain elbow The maximum protrusion of drain connection of elbow from the wall is 90mm 3 to allow for the covers The water supply ends in 2 two 90 shut off valves pointing downward not included The maximum protrusion of the shut off valves from the wall is 90mm 3 to allow for the covers It is important that all hoses for water connection and d...

Страница 13: ...1666 15mm Pipe Water hose extensions Hose from basin Coupling piece Extra hose 1 2 1 2 Item no 97001662 1 2 x 1 2 0 5m steel Item no 97001123 1 2 x 1 2 1m plastic Item no 97001120 Drain Drain pipe from basin Adapters Installation in room not included No adapter necessary Ø32 Ø32 Ø40 Item no 97001660 Ø40 Ø32 Ø50 Item no 97001661 Ø50 Drainpipe extensions Drainpipe from basin Coupling piece Extra dra...

Страница 14: ... 048 Frame Basic side bracket 1 one Ropox Support Washbasin Basic height adjustment left 40 44012 40 44010 064 Top plate with washbasin left oriented 1 one Basic height adjustment brackets 1 one set Incl 40 44010 025 Long bracket 40 44010 026 Short bracket 40 44010 020 Inside legs 97800 022 Threaded plate 97001631 Adjustable handles 40 44010 048 Frame Basic side bracket Ropox Support Washbasin Bas...

Страница 15: ...Manual 2 two sets Incl Cover Distance blocks 40 44010 038 Hexagonal shaft 1 one 20 60320 548 Hand crank 1 one Ropox Support Washbasin Manual height adjustment right 40 44015 40 44010 070 Top plate with washbasin right oriented 1 one Provided with Top frame right oriented 1 one Incl 40 44010 077 Frame Manual support right 40 44010 082 Hand crank assembly right 30 67600 Flexi legs Manual 2 two sets ...

Страница 16: ...4 Installation of product 4 4 1 Support Washbasin Fixed 40 44010 11 Recommended 6 x M8x72 6 x rawlplugs NOTE Depending on wall type choose other suitable screws as required Max load on upper screws 150 kg screw 256 150 405 320 ...

Страница 17: ...17 TF 200 01 0047_eng 4 4 2 Support Washbasin with Basic frame 40 4012 13 12 x M4x16 2 x M5 2 x M5x10 ...

Страница 18: ...7_eng Recommended 6 x M8x72 6 x rawlplugs 510 5 NOTE Depending on wall type choose other suitable screws as required Max load on upper screws 85 kg screw Fine adjustment of wall fitting use legs on washbasin as a guide ...

Страница 19: ...19 TF 200 01 0047_eng Plumbing kit is accessory ...

Страница 20: ...20 TF 200 01 0047_eng Mixer tap is accessory ...

Страница 21: ...21 TF 200 01 0047_eng 405 170 320 ...

Страница 22: ...22 TF 200 01 0047_eng 4 4 3 Mounting of covers for 40 44012 13 accessories 2 x 4 5x50 2 x rawlplugs ...

Страница 23: ...23 TF 200 01 0047_eng 2 x M4x10 6 x M4x16 ...

Страница 24: ...24 TF 200 01 0047_eng ...

Страница 25: ...25 TF 200 01 0047_eng 3 x M4x10 ...

Страница 26: ...26 TF 200 01 0047_eng 4 4 4 Support Washbasin with Manual frame 40 44014 15 4 x M8x20 ...

Страница 27: ...27 TF 200 01 0047_eng ...

Страница 28: ...28 TF 200 01 0047_eng 1 x M4 Allen wrench 2mm ...

Страница 29: ...29 TF 200 01 0047_eng 5mm 5mm 1 x M8x20 ...

Страница 30: ...30 TF 200 01 0047_eng Recommended 6 x M8x72 6 x rawlplugs NOTE Depending wall type choose other suitable screws as required Max load on upper screws 71 kg screw ...

Страница 31: ...31 TF 200 01 0047_eng Tip Move washbasin to top position to facilitate further mounting ...

Страница 32: ...32 TF 200 01 0047_eng 1 x M5x50 Plumbing kit is accessory Mixer tap is accessory ...

Страница 33: ...33 TF 200 01 0047_eng 320 400 ...

Страница 34: ...34 TF 200 01 0047_eng 4 4 5 Mounting of covers for 40 44014 15 2 x M8x72 1 x strips 2 x M4x10 ...

Страница 35: ...35 TF 200 01 0047_eng 6 x M4x16 ...

Страница 36: ...36 TF 200 01 0047_eng ...

Страница 37: ...37 TF 200 01 0047_eng 3 x M4x10 ...

Страница 38: ...e washbasin in a manner excluding the risk of damage to persons or property The person operating the washbasin is responsible for avoiding damage or injury If the washbasin is used in publicly accessible locations where children or persons with reduced observation capacity may get near it the person operating the washbasin must pay attention to those present in order to prevent dangerous situation...

Страница 39: ...s Note Do not use cleaning agents containing abrasive e g scouring powder steel wool scouring sponge This product is not designed to be sterilized autoclaving and sterilization beyond normal cleaning may possibly change the product safety and function 7 3 Inspection Note Failing to comply with periodic maintenance may result of degrading of product function and safety Note Ropox will make parts li...

Страница 40: ...e are no jammed objects preventing adjustment It takes too long for the water to leave the washbasin Check the siphon for clogging and clean it if required Check that the flexible hose on the wall has not been positioned so high that it acts as an extra siphon Cf recommendation section 6 Service and maintenance Serial No Date Signature Comments Service and maintenance Serial No Date Signature Comm...

Страница 41: ...onmental protection The product is not intended to be disposed as municipal waste Proper disassembly sorting and disposal of components must be done by waste disposal professionals Part Disposal recommendation Wash basin Ceramic Main unit Steel Mixer tap accessories Steel Cover accessories Plastic 11 Complaints See General Terms of Sale and Delivery on www ropox dk ROPOX A S Ringstedgade 221 DK 47...