RESM-4/RESM-5 Replacement

RESM-5 factory settings / as-shipped 
condition

By restoring the factory settings (step 21 in the
software menu, see step 10 above), you reset the unit
to the following defaults:

The selected language (step 201 in the software menu)
is not changed when you restore the factory settings.

As-shipped condition:

The RESM-5 monitoring unit is shipped with the above
factory settings and with the language set to "German".

Menu

Function

Value

107

AUTOCAL temperature

20°C

204

Alloy

400ppm/K

205

Range

300°C

206

Maximum temperature
(alarm threshold)

40°C

213

Key lock

No key

215

Alarm output

Normal 
(energized at 
alarm)

225

Temperature unit

Celsius

228

Screensaver

5min

229

ALARM-IN/RESET input

Normal

Содержание RESISTRON RESM-4

Страница 1: ... 4 and set the alarm threshold you do this on the RESM 5 with a display and four keys Older RESM 1 monitoring units for temperature controllers in the 2xx series cannot be converted using the RESM 5 Preparation 1 Select the unit Select an RESM 5 with the same line voltage as the old RESM 4 monitoring unit 115VAC 230VAC or 400VAC The RESM 5 monitoring unit has the following order numbers Line volta...

Страница 2: ...un AUTOCAL Old setting ranges on the RESM 4 AUTORANGE function on the RESM 5 The RESM 5 monitoring unit has no coding switches on the housing The voltage 0 4 120V and current 30 500A ranges are automatically set when you run the AUTOCAL function Heed the information provided in the ROPEX Application Report in order to avoid malfunctions 4 The number of times the wire is laid through the PEX W2 3 o...

Страница 3: ... higher level controller You should therefore only use this function if the risk analysis for the machine or plant allows To calibrate the zero point AUTOCAL on the RESM 5 Run the AUTOCAL function while the heatsealing band is cold Press the key repeatedly until menu step 107 is displayed Then select the AUTOCAL function by pressing the key If this function is executed correctly the main menu is a...

Страница 4: ...u is not changed when you restore the factory settings As shipped condition The RESM 5 monitoring unit is shipped with the above factory settings and with the language set to German Menu Function Value 107 AUTOCAL temperature 20 C 204 Alloy 400ppm K 205 Range 300 C 206 Maximum temperature alarm threshold 40 C 213 Key lock No key 215 Alarm output Normal energized at alarm 225 Temperature unit Celsi...

Страница 5: ...tion Power up message 208 Set point exceeded 206 Max temperature 210 Cooling mode 212 Relay K1 function 213 Key lock 207 Set point reached 205 Temperature range Setting Configuration 211 Heatslg time start Error 215 Alarm output 204 Temp coefficient 214 Cycles 107 Autocal 102 Preheat temp Autocal 5 6 209 Time control 1 2 216 Analog output 1 2 217 Temp diagnosis 218 Temp diag delay Continued on nex...

Страница 6: ...lacement 221 Autocomp 220 Meas imp length 219 Heatup timeout Configuration 222 Output 1 Continued from previous page Back to home position 225 Temperature unit 226 System time 227 Visualization 228 Screensaver 229 RESET input ...

Страница 7: ...rim U1 Twisted Auxilary power supply ANALOG OUTPUT actual value 0 10VDC 0V Internal ground NO EXTERNAL GROUNDIG ALLOWED Current transformer PEX W2 W3 11 10 IR NC NC NC NC 1 2 7 8 8 7 5 6 X Terminals on RESM 4 See RESM 5 documentation See RESM 5 documentation Note If error code 118 appears when you switch on the RESM 5 these cables should be reversed interchanged 9 10 11 or 12 13 14 or 15 Ground Mu...

Страница 8: ... coil HEATSEALING BAND Or from MAIN CONTROLLER RES UR CONTACT CONTACT LOGIC SIGNAL or 24VDC 0V signal 5 6 7 8 2 1 Twisted LINE 13 NO 12 9 11 10 14 NC 15 C ALARM OUTPUT RELAY max 100VDC 240VAC 1 5A ALARM INPUT FROM MAIN CONTROLLER ALARM OUTPUT RES MAIN CONTROLLER RESM 4 Relay energized in go state 0 24V In phase with RES controller ...

Отзывы: