RESM-4/RESM-5 Replacement
Page 3
10.
Configure the RESM-5:
Configure the RESM-5 as described in the
"Configuration" section of the product
documentation. The following settings must always
be configured:
Step nos. 204 (temperature range), 205
(heatsealing band alloy), and 206 (maximum
temperature) should be set according to the
heatsealing application and the heatsealing bands
used. To prevent dangerous situations, refer to the
risk analysis for the machine or plant.
11.
Deactivate alarms to simplify startup (if
necessary):
To start up the RESISTRON temperature controller
independently of the RESM-5 (e.g. in order to run
AUTOCAL), you can deactivate the alarm output of
the RESM-5 for a defined time. To do this, set any
time up to 5 minutes with step 215 (alarm output).
This time only applies once and is canceled if the
RESM-5 is switched on or off.
The alarm relay is no longer switched by the
RESM-5 if the alarm output is deactivated. In
this case, error messages/signals are no longer
transferred to the higher-level controller. You
should therefore only use this function if the risk
analysis for the machine or plant allows.
To calibrate the zero point (AUTOCAL) on the
RESM-5:
Run the AUTOCAL function while the heatsealing band
is cold.
Press the
key repeatedly until menu step 107 is
displayed. Then select the AUTOCAL function by
pressing the
key. If this function is executed
correctly, the main menu is automatically displayed
again.
If AUTOCAL was not performed successfully, an error
message appears on the display. In this case the
controller configuration is incorrect (
see
"Configuration" section of the RESM-5 documentation
and ROPEX Application Report). Configure the
controller correctly and run the AUTOCAL function
again.
The AUTOCAL function must be executed
correctly on the RESISTRON temperature
controller before it can be run here (i.e. the
RESISTRON temperature controller must generate
measuring impulses).
Setting
Step in
Configuration
menu
Language
201
Restore factory settings
202
Temperature range and
heatsealing band alloy
204, 205
Maximum temperature
(alarm threshold)
206
Alarm output function
215
ALARM-IN/RESET input function
229
!
The monitoring unit is
now ready
!
ENTER