Controller functions
Page 72
RES-440
Version 1
6.
"Active if Tact = Tset" (This setting is possible as of software revision 100)
Relay K1 is activated if the actual value is inside the specified temperature tolerance band (steps 207, 208). If
the actual temperature is outside the tolerance band, relay K1 is deactivated (see graph below).
7.
"Active if Tact = Tset", with latch function (This setting is possible as of software revision 100)
Relay K1 is closed if the actual value is inside the specified temperature tolerance band (steps 207, 208). If the
actual temperature leaves the tolerance band once during the heatsealing phase, relay K1 is opened. The relay
is not closed again until the next "START" signal is activated. The switching state of relay K1 can thus also be
interrogated by the higher-level PLC after a heatsealing process (latch function, see graph below).
10.23.8 “Output 1“/ “Temperature OK“ signal (with time control)
On controllers up to software revision 027, the switching output at terminals 20+21 was called
"Temperature OK". The more general name "Output 1" is used as of software revision 100 because
this output now also supports other functions.