Controller functions
Page 46
RES-440
Version 1
207
[24]
Set point reached
(low limit)
As of software revision 100:
If the actual value is greater than the switching
threshold specified here and less than the threshold
set with step 208, "Output 1" and/or relay K1 can be
activated depending on the configuration (step 212
or 222).
Up to software revision 027:
If the actual value is greater than the switching
threshold specified here and less than the threshold
set with step 25, the "Temperature OK" output is
activated.
The value is entered in Kelvins (K) and subtracted
from the set point in order to calculate the switching
threshold.
-5K…-99K
208
[25]
Set point exceeded
(upper limit)
As of software revision 100:
If the actual value is less than the switching
threshold specified here and greater than the
threshold set with step 207, "Output 1" and/or relay
K1 can be activated depending on the configuration
(step 212 or 222).
Up to software revision 027:
If the actual value is less than the switching
threshold specified here and greater than the
threshold set with step 24, the "Temperature OK"
output is activated.
The value is entered in Kelvins (K) and added to the
set point in order to calculate the switching
threshold.
+5K…+99K
209
[26]
Time control
This menu step specifies whether the controller
should operate with or without time control.
ON,
ON with START moni-
toring,
OFF
No.
Name
Description
Setting range