Accura 2300S/2350-1P3FSC User Guide
Chapter 4 Accura 2300S Operation/Setup
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 135
Event Log of the End of Current Event
For the current event that occurred, the duration and the maximum current measured during the event
are displayed.
Display
Description
Module[d][d]
1
ID of Accura 2350 module where the event occurred
E[d][d][d]
Event log number 000 - 999
A 1.Cr.E
Current event ends on the feeder 1
2
(A phase
2
).
[d][d][d][d] A
Maximum current [A] measured during the event
[d][d][d][d][d] ms
Current event duration time [ms]
1. d
→
decimal
2. It indicates the feeder(1, 2, 3) and the phase(A, B, C) where the event occurred.
Leakage Current Event Log
Leakage current measurement is supported only on Accura 2350-1P3FSC-DIZCT module.
Event Log of the Start of Leakage Current Event
Display
Description
Module[d][d]
1
ID of Accura 2350 module where the event occurred
E[d][d][d]
Event log number 000 - 999
2.L
ㅏ
.S
Leakage current event starts on the feeder 2.
2
[d][d][d][d] A
Leakage current [A] measured when an event occurs
1. d
→
decimal
2. It indicates the feeder(1, 2, 3) where the event occurred.
Event Log of the End of Leakage Current Event
For the leakage current event that occurred, the duration and the maximum current measured during
the event are displayed.
Display
Description
Module[d][d]
1
ID of Accura 2350 module where the event occurred
E[d][d][d]
Event log number 000 - 999
2.L
ㅏ
.E
Leakage current event ends on the feeder 2
2
.
[d][d][d][d] A
Maximum Leakage current [A] measured during the
event
[d][d][d][d][d] ms
Leakage current event duration time [ms]
1. d
→
decimal
2. It indicates the feeder(1, 2, 3) where the event occurred.