Part No 4801-5158 Rev 1-2017
RS500/600 Series Doors
Page 33
Warning!
Dangerous High Voltages!
Allow Approximately 5 Minutes For The Controller To Power-Down
Before Changing Switch Settings, Jumper Placement, Or Wiring.
Warning!
Use The Correct RS Door Brake Rectifier For The Specific Required Voltage!
Using A 230 VAC Brake Rectifier With A 115 VAC Power Supply Can Result In
Improper Door Operation Due To The Mechanical Brake Not Releasing Properly.
Using A 115 VAC Brake Rectifier With A 230 VAC Power Supply Can Result In
Damage To The Mechanical Brake And/Or Brake Rectifier Resulting In Door Failure.
The SC-325/SC-650 Controllers and RS-500/600 Doors can be field upgraded to accommodate either 115
VAC or 230 VAC power supply. If the desired power supply voltage is different from the factory
preset/prewired voltage, the appropriate version Brake Rectifier must be ordered separately, field-installed on
the RS Door, and the SC Controller switch and jumper settings changed accordingly.
Note!
If Your Serial # Comes After
‘0010156’,
You May Have A Motor
That Requires The
Blue W/White Stripe Wire
To Be Changed
From T8 & T2
To Now Use T9 & T3 Instead.
The Blue W/Red Stripe
Now Uses T8 And T2.
!
!
!
!
Содержание RS-500 Series
Страница 20: ...Page 20 RS500 600 Series Doors Part No 4801 5158 Rev 1 2017 AC DC Harness ...
Страница 31: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 31 Brake Rectifier Jumper ...
Страница 41: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 41 23 4 Matrix2 Loop Sensor ...
Страница 43: ...Part No 4801 5158 Rev 1 2017 RS500 600 Series Doors Page 43 ...
Страница 44: ...Page 44 RS500 600 Series Doors Part No 4801 5158 Rev 1 2017 ...