background image

4

Rollerdor RD10X2ELL Control Box,  Edition 2022/1

3. SETTING UP WIRELESS  

    SAFETY EDGE KIT

        (OPTICAL EDGE)

Pictures are for illustration purposes only, connector blocks are not provided and further fittings may be required. 

CHECKING BASE RAIL UNIT

CHECKING CONTROL BOX

LIMITS

Your base rail unit is already installed on the last slat of your 
curtain the same side as the power. it is a small black unit, 
undo all 3 screws and remove the lid 

(fig.7)

.

Check GREEN LED is on, wires are secure and are wired 
follows: Both banks of terminals from outside to in are 
Brown - White - Green 

(fig.8)

.

Control box Dip Switches: check dip switches on main board 

(fig.9)

 dip switch number 1 should be on and number 2 off.

The control box is supplied in Hold to Run operation for open and 
close, if the limits of the motor have not been set then please set 
them now using the P1 (UP) & P2 (Down) buttons 

(fig.9)

, if when 

you press and hold either of the buttons the unit just beeps then 
you will need to put the unit into Hold to Run by pressing and hold-
ing both P1 & P2 buttons at the same time until you hear a single 
beep 

(fig.10)

. Once you have finished setting limits once again 

press and hold both P1 & P2 buttons at the same time until you hear 
a single beep to return to single press operation.

fig.7

fig.8

fig.9

fig.10

Dip switches

P2

P1

Содержание RD10X2ELL

Страница 1: ...Rollerdor RD10X2ELL Control Box Edition 2022 1 Installation Guide for Roller Garage Doors RD10X2ELL Control Box Edition 2022 1...

Страница 2: ...e receiver box making sure to securely fix the cable out of the way of the working mechanism 4 The Glands at the bottom are for the cables to be inserted 1 motor wire 2 power wire 3 safety brake if su...

Страница 3: ...tion 2022 1 Pictures are for illustration purposes only connector blocks are not provided and further fittings may be required fig 4 Left Hand Motor fig 5 Safety Brake fig 6 No Safety Brake 2 ELECTRIC...

Страница 4: ...1 Control box Dip Switches check dip switches on main board fig 9 dip switch number 1 should be on and number 2 off The control box is supplied in Hold to Run operation for open and close if the limi...

Страница 5: ...ers 2 Channel 1 Press P1 PROG button two times on last press HOLD causing the buzzer to emit a continuous sound 2 Whilst P1 PROG is still pressed press the top button on the transmitter you will hear...

Страница 6: ...hear a continuous beep from the control box whilst holding the button press and hold Number 1 on the keypad the continuous beep will change to faster beep on hearing this release all buttons and the k...

Страница 7: ...ain is supplied with stops at each end to stop an uneven floor having an effect fig 13 but if the curtain reopens having hit the floor the safety edge exclusion should be set to turn off the edge 50mm...

Страница 8: ...8 Pictures are for illustration purposes only connector blocks are not provided and further fittings may be required 4 TROUBLESHOOTING...

Страница 9: ...orwich Norfolk NR5 9JD 44 0 1603 743215 sales rollerdor net www rollerdor net Company Registration Number 10676267 Registered Office Address Rollerdor Ltd Bankside 300 Peachman Way Broadland Business...

Отзывы: