 Digital Controller                                        PN 554135      07/11/19                                       Page: 15 of 24 

5.  Operation 

 

5.1 Startup  

 
Do not add chemicals to the feeders until all startup operations are completed. Using a DPD 
test kit, manually adjust and balance the water chemistry to acceptable ranges. Automation 
should be used to maintain chemical levels, not to balance a pool that is far out of 
acceptable ranges. With the controller in the OFF mode, turn the filter pump on and check 
for leaks in the system and flow through the flow cell. The flow lamp will be illuminated if the 
controller has power, it is connected to the flow switch and there is adequate flow. If a flow 
switch is not attached, the flow lamp will be illuminated if there is a jumper in the Flow 
Switch Terminal allowing the controller to be used without a flow switch. Using a flow switch 
is always recommended. 
 
A properly installed and functioning flow switch will disconnect power to chemical feeders if 
there is no water flow in the circulation plumbing. Test flow switch monthly by closing left-
hand valve on Flowcell and confirming that the flow light turns off. Then re-open valve and 
confirm that light turns back on. 
 
 

5.2 pH settings   

 
Press and release the controller MODE button until the pH LED is lighted (refer to the 
description of controls). Then select the desired Set Level, Feed Time and High and Low 
Alert Levels. Adjust Consecutive Feed Alert Limit if Set Level is not met within preset limit as 
indicated by the Digital Display flashing. –See appendix for detail. 
 

 

Note: Controller can be set to feed acid or base. See Acid/Base pH chemical feed section 
in Appendix for Dip switch settings. To verify that acid feed mode is selected adjust the pH 
set level below the pH indicated on the display. The feed lamp should come on if the 
controller is in acid feed mode. To verify that base mode is selected adjust the pH set level 
above the pH indicated on the display. The feed lamp should come on if the controller is in 
base feed mode. 

 

5.3 pH Calibration 

 
The pH sensor can drift slightly over time and calibration will offset this drift. Always calibrate 
using water from the sample port of the flow cell and use an independent pH test method to 
determine pH value of sample, unless using preset buffer solution. Press and release the 
controller MODE button until the pH LED is lighted (refer to the description of controls). Then 
use pH CALIB button to adjust reading to match known pH value of sample. It may take up 
to 24 hours for the sensors to acclimate to the system so recalibrate 24 hours after the first 
calibration. The pH sensor calibration should be checked every four to six weeks. If 
calibration is required more often then probe may need cleaning or replacement. 

 

 

 

Содержание RC554XP

Страница 1: ...f 24 F MODE FEED ONCE pH AUTO ORP LEVEL SET pH FEED ALERT CALIB pH FEED TIME HI ORP LOW ORP FEED L O W ALERT pH Operating Manual MODEL RC554XP ORP pH Digital Controller IMPORTANT SAFETY INSTRUCTIONS R...

Страница 2: ...lso remove power from the controller Provide a properly located outlet controlled by the circulating pump circuit 1 6 WARNING Risk of electric shock pinching chemical exposure Remove power sources or...

Страница 3: ...allation 4 1 Locating the controller 12 4 2 Mechanical installation 12 4 3 Power panel access 13 4 3 1 Dip switches 13 4 3 2 Fuses 13 4 3 3 Flow switch 13 4 3 4 Globe Flowcell 14 5 Operation 5 1 Start...

Страница 4: ...ings Press and release the MODE button until the desired ORP or pH LED is lit Once the settings are changed they will remain at those settings until they are changed again Set level press the SET LEVE...

Страница 5: ...isplay resolution The ORP set point is adjustable from 400 to 900 mV with default set point of 650 mV During an ORP feed cycle the ORP feed lamp will flash when sanitizer chemicals are being fed and i...

Страница 6: ...nternal terminal strip is provided for field wiring of the controller The internal step down transformer has a class two energy limiting rating to provide for electrical safety Note When automating an...

Страница 7: ...s Terminal strip for hardwire applications included Displays ORP and pH red digital Power and flow indicator LED Alert indicator Feed indicator LED ORP pH Mode indicator LED pH ORP Auto Note feed lamp...

Страница 8: ...onitors pH and ORP and displays programmed set points The Digital Display numbers will flash if Consecutive Feed Alert Limit is exceeded 5 pH STANDBY LAMP AND PROGRAMMING BUTTONS When pH standby lamp...

Страница 9: ...set desired pH parameters Note When scrolling through the set modes to reverse the direction simply release the button momentarily and press the button again Feed Once button By pressing the FEED ONCE...

Страница 10: ...calibration allows the adjustment of 1 pH in 1 pH increments Consecutive Feed Alert Limit The Digital Display numbers will flash and the pump feeder will not activate if the Set Level is not reached...

Страница 11: ...sed the ORP readout will scroll through the available ORP levels 100 mV to 640 mV in 5 mV increments and OFF Release the button when the desired level is reached The pH CALIB button is not functional...

Страница 12: ...oller in a location accessible to the public Install the controller in an area protected from natural elements sun rain freezing etc See appendix for typical feed system schematics 4 2 Mechanical Inst...

Страница 13: ...These fuses are located inside the lower panel The fuse holders are shipped with 5 amp fuses Replacement fuses are 5mm x 20mm Fast Acting IEC 4 3 3 Flow Switch The controller has a flow switch termina...

Страница 14: ...perate as a power light It is recommended the jumper be retained to assist in troubleshooting if necessary 4 3 4 Globe Flowcell see Globe Flowcell Operating Manual Connect the Globe Flowcell grounding...

Страница 15: ...description of controls Then select the desired Set Level Feed Time and High and Low Alert Levels Adjust Consecutive Feed Alert Limit if Set Level is not met within preset limit as indicated by the D...

Страница 16: ...troller with ROLA CHEM pumps the pump switch should be in the CONTINUOUS position not Timed or Off If the sanitizer level is too low or high adjust the ORP set level up or down in small increments for...

Страница 17: ...eed time is 0 6 sec on with 5 minute delay Feeders may require longer feed time If time is too short set points will not be maintained If feed time is too long overfeeding chemicals may occur Correct...

Страница 18: ...ight should be on F Press MODE to turn the controller On and return to operating mode The last two steps are extremely important because this puts the controller back in operating mode If these two st...

Страница 19: ...switch flow cell valves feeders tubing etc are not covered under this warranty Heavy duty probes are warranted from the date of original purchase for one 1 year ROLA CHEM under no circumstances shall...

Страница 20: ...in the timed feed mode 1 Turn off remove power then move 2 dip switch to ON 2 Re power press MODE to set it for ORP or pH 3 Note feed time setting then Set FEED TIME to OFF 4 Press FEED ONCE button t...

Страница 21: ...he buttons D The controller is now in test mode Test mode reduces the feed delay time from 5 minutes to 5 seconds to simplify diagnostics E Turn the controller Off again to exit test mode F Turn the c...

Страница 22: ...ROLA CHEM Digital Controller PN 554135 07 11 19 Page 22 of 24 8 4 Typical System Installations...

Страница 23: ...ROLA CHEM Digital Controller PN 554135 07 11 19 Page 23 of 24 8 4 Typical System Installations cont...

Страница 24: ...ROLA CHEM Digital Controller PN 554135 07 11 19 Page 24 of 24 NOTES...

Отзывы: