ROLA-CHEM Digital Controller                                        PN 554135      5/04/2017                                                   Page: 13 of 20 

controller MODE button until the pH LED is lighted (refer to the description of controls). Then 
use pH CALIB button to adjust reading to match known pH value of sample. It may take up 
to 24 hours for the sensors to acclimate to the system so recalibrate 24 hours after the first 
calibration. The pH sensor calibration should be checked every four to six weeks. 

 

5.4 ORP settings 

 

 
Press and release the controller MODE button until the ORP LED is lighted (refer to the 
Description of Controls section).  Then select the desired Set Level, Feed Time and Hi and 
Low Alerts. 
 
The ORP display indicates the effectiveness of the sanitizer; it does not directly correlate to 
a chlorine ppm reading. To determine your ORP set level, manually adjust and balance the 
pool to be within acceptable ranges. Use a DPD test kit to confirm the free chlorine level. 
Use the ORP reading of the balanced pool as your ORP set level. 

 

5.5 Operating mode

 

 
Press and release the MODE button until the AUTO LED is lighted. This is the operational 
mode for the controller. The controller must be in this mode for the feeders to maintain the 
desired parameters.  

 
Note: When using the RC554XP or 554000 controller with ROLA-CHEM pumps, the pump 
switch should be in the CONTINUOUS position (not Timed or Off). 

 

If the sanitizer level is too low or high, adjust the ORP set level up or down in small 
increments (for example 10mV to 25 mV increments) to lock in the desired sanitizer level.  
 

Note: The ORP reading is highly dependent on both the pH and the cyanuric acid levels. 
Both of these variables must be kept within acceptable ranges to maintain an acceptable 
relationship between the ORP and the ppm of the sanitizer.   
 
Note: Low feed rates can cause the feeder to lag or feeding to be extended. A high feed 
rate can result in too much chemical being added. 
 

If using time feed cycle, the feed lamp will flash during the feed time and be lit continuously 
during the delay time of the feed cycle. If over feeding is occurring, consider using a shorter 
feed cycle. 

 

In Continuous feed, the feed lamp will flash while feeding. 

 

The pump will not activate when an alert lamp is on indicating readings below or above the 
alert settings. 

 

 

 

 

Содержание RC554000

Страница 1: ...F MODE FEED ONCE pH AUTO ORP LEVEL SET pH FEED ALERT CALIB pH FEED TIME HI ORP LOW ORP FEED L O W ALERT pH Operating Manual MODELS RC554XP AND 554000 ORP pH Digital Controller IMPORTANT SAFETY INSTRUC...

Страница 2: ...lso remove power from the controller Provide a properly located outlet controlled by the circulating pump circuit 1 6 WARNING Risk of electric shock pinching chemical exposure Remove power sources or...

Страница 3: ...ols 7 4 Installation 4 1 Locating the controller 10 4 2 Mechanical installation 10 4 3 Power panel access 11 4 3 1 Dip switches 11 4 3 2 Fuses 11 4 3 3 Flow switch 11 5 Operation 5 1 Startup 12 5 2 pH...

Страница 4: ...low pH 8 0 high 7 0 low To Change Settings Press and release the MODE button until the desired ORP or pH LED is lit Once the settings are changed they will remain at those settings until they are chan...

Страница 5: ...ontinuously during the feed delay portion of the feed cycle The ORP Alert lamp will illuminate when the ORP reading is higher or lower than the high and low ORP Alert set points and prevent the feedin...

Страница 6: ...ire grounded power cord Combined load not to exceed 10 amps GFCI source required Output Power 120 Volts AC 50 60 HZ 5 amps fused for both ORP and pH Two 3 wire grounded power receptacles Terminal stri...

Страница 7: ...ing feed delay 4 pH ORP DIGITAL DISPLAYS Monitors pH and ORP and displays programmed set points 5 pH STANDBY LAMP AND PROGRAMMING BUTTONS When pH standby lamp is illuminated the six set buttons are en...

Страница 8: ...ssing the FEED ONCE button the pH feeder will feed and delay for one complete feed cycle See FEED TIME Button for feed delay times If the Feed time is set for Continuous feed the manual feed will not...

Страница 9: ...ET LEVEL button which displays in 5 mV increments until the desired level is reached Feed Time The feed times are displayed in seconds There is a five 5 minute delay time associated with each feed tim...

Страница 10: ...roller in a location accessible to the public Install the controller in an area protected from natural elements sun rain freezing etc See appendix for typical feed system schematics 4 2 Mechanical Ins...

Страница 11: ...dix for settings 4 3 2 Fuses The ORP and pH are independently fused to protect the controller from defective feeders These fuses are located inside the lower panel The fuse holders are shipped with 5...

Страница 12: ...n the OFF mode turn the filter pump on and check for leaks in the system and flow through the flow cell The flow lamp will be illuminated if the controller has power it is connected to the flow switch...

Страница 13: ...until the AUTO LED is lighted This is the operational mode for the controller The controller must be in this mode for the feeders to maintain the desired parameters Note When using the RC554XP or 5540...

Страница 14: ...affected by pH probe Both probes must be in good operating condition 6 3 Set points not being reached maintained Factory setting for feed time is 0 6 sec on with 5 minute delay Feeders may require lo...

Страница 15: ...and return to operating mode The last two steps are extremely important because this puts the controller back in operating mode If these two steps are not performed the controller will remain in test...

Страница 16: ...are not covered under this warranty Heavy duty probes are warranted from the date of original purchase for one 1 year ROLA CHEM under no circumstances shall be liable for any consequential damages di...

Страница 17: ...eed Alert Limit feature in the timed feed mode 1 Turn off remove power then move 2 dip switch to ON 2 Re power press MODE to set it for ORP or pH 3 Set FEED TIME to OFF 4 Press FEED ONCE to select the...

Страница 18: ...mode shortens minutes to seconds E Turn the controller Off again to exit test mode F Turn the controller On to return to operating mode The last two steps are extremely important because this puts th...

Страница 19: ...CLEAR OF DEBRIS FLOWSWITCH EARTH GROUND WATER TO POOL ACID PUMP HEATER ACID HCl MANIFOLD FLOWSWITCH VALVE EARTH GROUND WATER FROM POOL WATER TO POOL EARTH GROUND SYSTEM USING EROSION FEEDER TRI CHLOR...

Страница 20: ...FROM POOL BASKET POOL PUMP FILTER CONTROLLER FLOWSWITCH CELL WATER TO POOL SPDT 120 VAC COIL RELAY COM NO NC MANIFOLD FLOWSWITCH STRAINER VALVE SAFETY FLOWSWITCH TO ENSURE CIRCULATION TO CONTROL PROB...

Отзывы: