Advanced Communication Module - Installation Guide
35
Terminal Block Wiring
Terminal
Description
AUX RED
COM BLK
BUS YEL GRN
Used to connect the ACM to the ProSYS
Panel board (the terminals are connected in
parallel to the panel BUS connector).
COM BLK
BUS 2 YEL2
GRN2
Provision for optional functionality
TIP, RING
Used for PSTN telephone line connection
(for ACM version that includes the modem
option).
Jumper Settings
Jumper
Description
STAND ALONE
Used to enable a local U/D connection to the
ProSYS using a local PC, while the ACM is
connected to the BUS.
2 pins configuration: The ACM U/D channel
is disabled, and a local U/D connection to the
ProSYS Bus is enabled.
NOTE:
Sending information from the
panel via the ACM is
functioning normally.
1 pin (default): Local U/D connection to the
ProSYS Bus is disabled, and the ACM
channel is enabled.
DFLT
Used to restore the default software provided
by the manufacturer (e.g. when remote
software upgrade fails).
2 pins configuration: Enables restoring of
the default manufacturer’s software.
To restore the ACM to the default
manufacturers software:
1)
Disconnect power from the ACM
2)
Place the DFLT jumper on its 2 pins.
3)
Reconnect the power to the ACM.
1 pin (default): Restoring of the default
manufacturer’s software is not enabled.