PRT42 and PRT42-BK v1.0 fv72 EN Rev.C 
 
 

 5 
 
 
 

3

 

O

P E R A T I N G  

M

O D E S

 

3.1

 

Host-controlled Operation (ONLINE mode) 

In ONLINE mode, a PRT terminal is controlled by a master unit (ACU). The terminal handles card and/or PIN 
code reading and then transmits the collected data to its master unit for further processing. A PRT terminal 
offers the following communication interfaces (data transmission formats): 

 

Wiegand 26bit 

 

Wiegand 34bit 

 

Wiegand 42bit 

 

Wiegand 66bit  

 

Magstripe (ABA Track II emulation) 

 

RACS (Roger) 

In case of Wiegand data formats there are several further settings to be configured which specify the method of 
PIN code transmission technique. The RACS format is designed for use with ROGER PRxx1/PRxx2 series ACUs. 

3.1.1

 

Wiegand Data Transmission Format 

 

When employing Wiegand transmission format, data are 
transferred using sequences of pulses sent over the CLK and DTA 
lines. Depending on the selected version of the transmission 
format, the PRT reader uses 26, 34, 42 or 66 bits to transmit a 
code read in from the presented card or a PIN entered. 
 

Note: For card and PIN codes longer than the number of bits 
available in the selected data transmission format a PRT reader 
omits the most significant bits of the data transmitted. As a 
result you may see different card number or PIN as expected. 

Generally, transmission of PIN codes to ACU can be carried out in 
two ways: one is to transmit the entire PIN code as one data 
frame; the other is to transmit it in separate parts, each 
containing a code of a single key pressed (for more details about 
PIN code transmission using Wiegand formats see table 2). 
 

When using Wiegand format, the dual color LED STATUS lights steady in RED, the LED SYSTEM is turned ON for 
a moment each time the card or PIN code is read. The LED OPEN is controlled by the IN1 input line. When IN1 
is shorted with supply minus the LED OPEN turns ON and the internal BUZZER sounds, when IN1 is shorted 
with supply plus or left unconnected LED OPEN and BUZZER are not active. 

DT

A

DA

TA

 1

CL

K

DA

TA

 0

IN

1

PRT Series Reader

Configured for Wiegand 

Interface

Wiegand

ACU

Содержание PRT42

Страница 1: ...Installation and Programming Guide PRT42 and PRT42 BK Indoor Access Control Terminals Firmware v72 00...

Страница 2: ...ory Reset Procedure Programming MASTER and INSTALLER cards 10 5 2 1 Factory Default Settings 10 5 3 Installer Programming Mode 10 5 4 User Programming Mode 11 5 4 1 Programming Commands 11 5 4 2 Progr...

Страница 3: ...other uses them for communication with an external XM 2 I O module and a second PRT reader see wiring diagrams An access control installation containing two PRT readers one at the entry the other at...

Страница 4: ...the PRT reader uses 26 34 42 or 66 bits to transmit a code read in from the presented card or a PIN entered Note For card and PIN codes longer than the number of bits available in the selected data t...

Страница 5: ...l LEDs are flashing it indicates that the reader lost communication with host ACU unit Each entry of PIN code must be followed by pressing the key which is treated as an end of PIN code The PRT42 read...

Страница 6: ...set to ID 0 Note The XM 2 I O expander module connected to PRT reader must be set to address ID 5 jumpers JP1 and JP3 closed 3 2 2 Simple stand alone operation mode In this mode the reader s CLK and...

Страница 7: ...s with two readers to be mounted on opposite sides of the same wall and along the same geometrical axis place a metal plate between them and make sure none of them has direct contact with it at least...

Страница 8: ...ethods and functions described for the keypad readers are also valid for the no keypad readers the only difference being that one press of a desired key on keypad reader is simulated on a no keypad re...

Страница 9: ...function Reader Disarmed Output User identification mode on the primary reader Card or PIN User identification mode on the secondary reader Card or PIN Option Door Alarm Indication On Internal Buzzer...

Страница 10: ...activates door lock 3 Ready Input when line shorted to supply minus reader can be armed C10 0 1 Primary main Reader Identification Mode 0 Card or PIN identification 1 Card PIN identification C11 0 1 S...

Страница 11: ...r with the specified ID and then deletes both his PIN and his card Once completed a new user can be programmed to use this ID index 0 Delete all users in the system Deletes all users including their c...

Страница 12: ...gramming command Example 5 Rearm the reader by presenting a TOGGLE User card Read your TOGGLE User card once accepted the reader grants you access and its SYSTEM LED starts blinking With the SYSTEM LE...

Страница 13: ...Mode INSTALLER user has no PIN code MASTER A card of this user allows to enter User Programming Mode MASTER user has no PIN code NORMAL Users of this type are solely authorized to unlock the door The...

Страница 14: ...D mode and has set an option Access Disabled When Reader Armed If the second scenario occurs the TOGGLE or TOGGLE LTD user may use its identifier Card PIN or both when Card PIN mode is active to switc...

Страница 15: ...on Memory error or MASTER or INSTALLER cards not programmed memory reset necessary This signal is accompanied by LED SYSTEM steady ON Legend one long signal One short signal beep LED Indications in St...

Страница 16: ...tion Interface The reader operates in Host controlled mode it needs to be connected to a master unit ACU which requires Magstripe data format ONLINE Mode 26 bit WIEGAND Communication Interface The rea...

Страница 17: ...s compatible with HID 5355 series readers option With Parity Each key transmitted separately no control bits added Each key pressed on the reader s keypad is immediately transmitted to the master cont...

Страница 18: ...PRT42 Grey RFID PIN reader light grey PRT42 BK Grey RFID reader light grey RM 2 Relay module The RM 2 offers two relays with one NO NC contact 5A 24V rated relay contacts protected with overvolatge e...

Страница 19: ...me Reader location ID Number Card number PIN Type User Name Master Installer 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 4...

Страница 20: ...name Reader location ID Number Card number PIN Type User Name 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 1...

Страница 21: ...PRT42 and PRT42 BK v1 0 fv72 EN Rev C 22...

Страница 22: ...PRT42 and PRT42 BK v1 0 fv72 EN Rev C 23...

Страница 23: ......

Страница 24: ...PRT42 and PRT42 BK v1 0 fv72 EN Rev C 25...

Страница 25: ...PRT42 and PRT42 BK v1 0 fv72 EN Rev C 26...

Страница 26: ......

Страница 27: ...tacking networks Roger does not warrant that the Product will be free of vulnerability to intrusion or attack This warranty does not cover repair or replacement where normal use has exhausted the life...

Страница 28: ......

Страница 29: ...may be reached at 48 55 2670126 or support roger pl Monday through Friday 8 00 A M to 4 00 P M GMT 1 You can also contact the Technical Support Department by fax at 48 55 2720133 If it is determined t...

Страница 30: ...form in order to avoid damages during transit You are advised to get proof of delivery 12 Some repairs may be chargeable and you will receive formal advice if this is the case 13 If product returned a...

Отзывы: