MCX402-BRD  is  I/O  expander  dedicated  to  the  RACS  5  system.  Depending  on  uploaded  firmware  the 
expander  operates  with  two Wiegand  interface  terminals  or  two  PRT  series  terminals.  After  connection  to 
MC16 controller the device enables to control single door. The expander operates with backup battery which 
can  be  charged  with  0.3A  current.  MCX402-BRD  expander  is  offered  separately  or  as  a  component  of 
MC402-1-KIT and MC402-2-KIT. 

Characteristics 

  RACS 5 system I/O expander 

  Power supply distribution for door devices 

  8 NO/NC inputs 

  2 transistor outputs 

  2 relay outputs 

  2 power supply outputs 

  Backup battery charging 

  RS485 interface 

  Wiegand interface 

  RACS CLK/DTA interface 

  Screw terminals 

Power supply 

The expander can be supplied with 24VDC or 18VAC and in such scenario it offers 13.8VDC power supply 
outputs (AUX, TML)  and backup battery  charging. Alternatively the  expander can be supplied  with 12VDC 
but then it does not offer power supply outputs and battery charging.  
The expander charges  backup battery  with 300mA stabilized current  up  to 13.8V.  Backup power supply  is 
activated automatically in case of main powers supply shortage. If the voltage at backup battery drops below 
approx.  10V  then  the  battery  is  automatically  disconnected  from  expander  and  remains  disconnected  until 
mains power supply returns. 

Note: MCX402-BRD expander cannot be started using only power supply from backup battery. 

 

Fig. 1 MCX402-BRD power supply 

RS485 bus 

The communication method with MC16 access controller is provided with RS485 bus which can encompass 
up to 16 devices of RACS 5 system, each with unique address in range of 100-115. The bus topology can 
be  freely  arranged  as  star,  tree  or  any  combination  of  them  except  for  loop.  The  matching  resistors 
(terminators)  connected  at  the  ends  of  transmitting  lines  are  not  required.  In  most  cases  communication 
works  with  any  cable  type  (standard  telephone  cable,  shielded  or  unshielded  twisted  pair  etc.)  but  the 
recommended  cable  is  unshielded  twisted  pair  (U/UTP  cat.5).  Shielded  cables  should  be  limited  to 

Содержание MCX402-BRD

Страница 1: ...Roger Access Control System MCX402 BRD Operating Manual Product version 1 0 Firmware version 1 0 4 or newer Document version Rev D ...

Страница 2: ...supplied with 12VDC but then it does not offer power supply outputs and battery charging The expander charges backup battery with 300mA stabilized current up to 13 8V Backup power supply is activated automatically in case of main powers supply shortage If the voltage at backup battery drops below approx 10V then the battery is automatically disconnected from expander and remains disconnected until...

Страница 3: ...arming mode of Alarm Zone armed disarmed OPN Green Door unlocked SYS Orange Various signalling functions including errors LINK Green Data transmission on RS485 bus Inputs Expander offers 8 inputs IN1 IN8 of NO and NC type Input types are defined within low level configuration RogerVDM Input functions are assigned within high level configuration VISO Multiple functions can be assigned to the same i...

Страница 4: ... battery P1 24VDC input power supply P2 Ground AUX 12VDC 1 0 output power supply for door lock TML 12VDC 0 2A output power supply for readers IN1 IN8 Input lines GND Ground IO1 IO2 15VDC 1A transistor output lines A B RS485 bus CLK DTA RACS CLK DTA bus NO1 COM1 NC1 30V 1 5A DC AC REL1 relay NO2 COM2 NC2 230V 5A AC REL2 relay ...

Страница 5: ...both devices must be connected with any wire 3 OPERATION SCENARIOS In typical scenario of operation MCX402 BRD expander is used to control single door by MC16 controller Depending on uploaded firmware the expander can operate with 2 Wiegand or PRT terminals In practical applications expanders are usually installed within MCX402 1 KITs The MCX402 2 KIT which is additionally equipped with PS1A modul...

Страница 6: ...MCX402 BRD Operating Manual 04 12 2020 6 13 Fig 4 Scenario of operation with MCX402 1 KITs Fig 5 Scenario of operation with MCX402 2 KIT ...

Страница 7: ...MCX402 BRD Operating Manual 04 12 2020 7 13 Fig 6 Typical door control with Wiegand readers ...

Страница 8: ...VDM program select MCX v1 x device firmware version RS485 communication channel and serial port with RUD 1 interface 3 Click Connect the program will establish connection and will automatically display Configuration tab 4 Enter unoccupied RS485 address in range of 100 115 enable Wiegand or PRT terminals configure input types e g NC for IN5 according to fig 6 and other settings according to require...

Страница 9: ...tered with keypad When set to 0 then PINs are disabled Range 0 8 Default value 4 Max PIN length Parameter defines maximal number of digits in PIN When set to 0 then PINs are disabled Range 0 8 Default value 8 key clears PIN buffer Parameter defines if already entered digits of PIN can be deleted with key Range Yes No Default value Yes Time between keys in PIN s Parameter defines max time between t...

Страница 10: ...n Wiegand terminal 1 2 is operated Range Yes No Default value Yes AF type Parameter defines authentication factor type returned by terminal Default value 16 Number 40bits AF class Parameter defines authentication factor class returned by terminal Default value 0002 EM KBD comment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program CDI comment...

Страница 11: ...ault MCX402DR WGx hex firmware is uploaded to expander PRT readers settings are available when MCX402DRx hex firmware from www roger pl is uploaded to expander Manual addressing The RS485 address of expander configured with RogerVDM is a software address Alternatively hardware RS485 address can be configured with jumpers and such address has higher priority than software address Note Each time the...

Страница 12: ...lated by RUD 1 interface and the option USB RS485 Converter 6 Select firmware file hex click Program and follow instructions on screen 7 Once the firmware is uploaded remove the FDM jumper and restart the device 8 Start Memory reset procedure 6 SPECIFICATION Table 4 Specification Supply voltage Nominal 18VAC min max range 17 22VAC Nominal 12VDC min max range 10 15VDC Nominal 24VDC min max range 22...

Страница 13: ...ct This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of pu...

Отзывы: