MCX102-BRD Operating Manual 

  

04.12.2020 

 

2/12 

 

1.

 

D

ESIGN AND APPLICATION

 

MCX102-BRD  is  I/O  expander  dedicated  to  the  RACS  5  system.  The  expander  operates  with  two  PRT 
series  terminals  or  single  terminal  with Wiegand  interface.  After  connection  to  MC16  controller  the  device 
enables to control single door. 

Characteristics 

  RACS 5 system I/O expander 

  2 NO/NC inputs 

  1 transistor outputs 

  1 relay outputs 

  RS485 interface 

  Wiegand interface 

  RACS CLK/DTA interface 

  Screw terminals 

Power supply 

The expander requires 12VDC power supply. The supply wire diameter must be selected in such way that 
the voltage drop between supply output and the device would be lower than 1V. The proper wire diameter is 
especially  critical  when  device  is  located  in  long  distance  from  the  supply  source.  The  minus  terminal  of 
such  PSU  should  be  connected  with  MC16  controller  GND  terminal  by  means  of  signal  wire  with  any 
diameter. It is recommended to install PSU near the expander, preferably inside ME series enclosure. 

RS485 bus 

The communication method with MC16 access controller is provided with RS485 bus which can encompass 
up to 16 devices of RACS 5 system, each with unique address in range of 100-115. The bus topology can 
be  freely  arranged  as  star,  tree  or  any  combination  of  them  except  for  loop.  The  matching  resistors 
(terminators)  connected  at  the  ends  of  transmitting  lines  are  not  required.  In  most  cases  communication 
works  with  any  cable  type  (standard  telephone  cable,  shielded  or  unshielded  twisted  pair  etc.)  but  the 
recommended  cable  is  unshielded  twisted  pair  (U/UTP  cat.5).  Shielded  cables  should  be  limited  to 
installations  subject  to  strong  electromagnetic  interferences.  The  RS485  communication  standard  used  in 
the RACS 5 system guarantees  proper communication in a distance  of up to 1200 meters as  well  as high 
resistance to interferences. 

Note: Do not use more than single pair in UTP cable for RS485 communication bus. 

Wiegand bus 

Wiegand  interface  can  be  used  for  communication  with  third  party  readers  and  terminals.  Wiegand 
communication is ensured via expander input lines (IN1, IN2) and single Wiegand terminal can be controlled 
in such way by MC16 controller. 

RACS CLK/DTA bus 

The  expander  enables  the  control  of  two  PRT  series  readers  with  ID=0  and  ID=1  addresses  by  MC16 
controller. 

LED indicators 

Expanders are equipped with LED indicators which are used to signal integral functions. 

Table 1. LED indicators 

Indicator 

Colour 

Integral function 

STA 

Red/ green 

Current arming mode of Alarm Zone (armed/disarmed) 

OPN  

Green 

Door unlocked 

SYS 

Orange 

Various signalling functions including errors 

Содержание MCX102-BRD

Страница 1: ...Roger Access Control System MCX102 BRD Operating Manual Product version 1 0 Firmware version 1 0 4 or newer Document version Rev A...

Страница 2: ...pology can be freely arranged as star tree or any combination of them except for loop The matching resistors terminators connected at the ends of transmitting lines are not required In most cases comm...

Страница 3: ...tion RogerVDM Function are assigned to outputs within high level configuration VISO Multiple functions with different priorities can be assigned to the same output at the same time 2 INSTALLATION Each...

Страница 4: ...plied from the same PSU then GND terminals of both devices must be connected with any wire 3 OPERATION SCENARIOS In typical scenario of operation MCX102 BRD expander is used to control single door by...

Страница 5: ...ating Manual 04 12 2020 5 12 Fig 3 Scenario of operation with MCX102 BRD expanders Note The enclosure ME 2 D offers enough space and PSU to install up to three MCX102 BRD expanders in order to control...

Страница 6: ...MCX102 BRD Operating Manual 04 12 2020 6 12 Fig 4 Typical door control with PRT series readers...

Страница 7: ...RogerVDM program select MCX v1 x device firmware version RS485 communication channel and serial port with RUD 1 interface 3 Click Connect the program will establish connection and will automatically d...

Страница 8: ...er Range Yes No Default value Yes Min PIN length Parameter defines the minimal number of digits for PIN entered with keypad When set to 0 then PINs are disabled Range 0 8 Default value 4 Max PIN lengt...

Страница 9: ...I BUZZER LED SYSTEM LED OPEN LED STATUS comment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program Wiegand terminal 1 Terminal enabled When opt...

Страница 10: ...restores factory default settings including ID 100 software address Expander memory reset procedure 1 Remove all connections from A B CLK and DTA terminals 2 Place jumper on 64 contacts and restart d...

Страница 11: ...isolated NO NC contact 30V 1 5A max load Transistor output Single OUT1 transistor output max load 15VDC 150mA Distances Up to 1200 m between controller and expander RS485 Up to 150m between expander a...

Страница 12: ...ectric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste con...

Отзывы: