HRT82TS Installation Guide Rev.C.doc
2016-10-10
8/9
Fig. 8 Firmware update window in RogerVDM software
4.3 Memory reset
In order to restore HRT82TS factory default settings place jumper on MEM pins and then restart the
device either by placing and removing jumper on RST pins or by switching power supply off and on.
Moreover, memory reset is also part of connection and configuration procedure (see 4.1).
5.
T
ROUBLESHOOTING
Table 4. Troubleshooting
Issue
Visual indication
Acoustic
indication
Solution
No
communication
with controller
Front panel icon
backlight blinking.
-
1. Check if RACS CLK/DTA bus is
properly connected, wires are
undamaged and the bus does
not exceed 150 m. All devices
connected to particular RACS
CLK/DTA bus should have
common supply minus (GND).
2. Check if the controller is
properly configured for
communication with the device.
6.
O
RDERING INFORMATION
Table 5. Ordering information
HRT82TS
Temperature sensor module
RUD-1
Communication interface with 12VDC power supply output