38
High Fd Prss
Shtdwn
High Feed
Pressure Shut
Down Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the high pressure alarm
is activated.
39
High Prm Prss SP
High
Permeate
Pressure
Setpoint
0-100
00
50
Pressure setpoint (in psig) which
activates the high pressure alarm.
40
High Prm Prss DB
High
Permeate
Pressure
Deadband
0-10
0.0
5
Deadband (in psig) through which the
pressure value must pass before the
high pressure alarm is released.
41
High Prm Prss TD
High
Permeate
Pressure
Time Delay
0-255
000
20
Delay (in seconds) before the high
pressure alarm is activated once the
current value rises above the setpoint.
42
High Prm Prss
Shtdwn
High
Permeate
Pressure Shut
Down Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the high pressure alarm
is activated.
43
High DP1 Prss SP
High
Differential
Pressure
Setpoint
0-100
00
50
Pressure setpoint (in psid) which
activates the high differential pressure
alarm.
44
High DP1 Prss DB
High
Differential
Pressure
Deadband
0-10
0.0
5
Deadband (in psid) through which the
pressure value must pass before the
high differential pressure alarm is
released.
45
High DP1 Prss TD
High
Differential
Pressure
Time Delay
0-255
000
20
Delay (in seconds) before the high
differential pressure alarm is activated
once the current value rises above the
setpoint.
46
High DP1 Prss
Shtdwn
High
Differential
Pressure Shut
Down Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the high differential
pressure alarm is activated.
47
High DP2 Prss SP
High
Differential
Pressure
Setpoint
0-100
00
50
Pressure setpoint (in psid) which
activates the high differential pressure
alarm.
48
High DP2 Prss DB
High
Differential
Pressure
Deadband
0-10
0.0
5
Deadband (in psid) through which the
pressure value must pass before the
high differential pressure alarm is
released.
49
High DP2 Prss TD
High
Differential
Pressure
Time Delay
0-255
000
20
Delay (in seconds) before the high
differential pressure alarm is activated
once the current value rises above the
setpoint.
50
High DP2 Prss
Shtdwn
High
Differential
Pressure Shut
Down Delay
0-255
000
10
Delay (in seconds) before the system
shuts down after the high differential
pressure alarm is activated.
51
Flow Activate
Flow Input
Activation
0 or 1
0
0
This setting activates all flow sensor
inputs and associated alarms. Flow
display screen is not accessible when
Flow inputs are not activated. Enter [0]
to deactivate flows or [1] to activate
flows.
52
Flw1 Config
Configuration
of Flow
Sensor 1
0 or 1
0
0
This setting configures the use of the first
flow sensor. Enter [0] to use the sensor
on feed or [1] to use the sensor on
permeate.
3-7