English-14
The PowerFlex 40 is designed so that start up is simple and efficient. The Program Group
contains the most commonly used parameters.
Display Group Parameters
No.
Parameter
Min/Max
Display/Options
d001 [Output Freq]
0.0/[Maximum Freq]
0.1 Hz
d002 [Commanded Freq]
0.0/[Maximum Freq]
0.1 Hz
d003 [Output Current]
0.00/(Drive Amps
×
2)
0.01 Amps
d004 [Output Voltage]
0/Drive Rated Volts
1 VAC
d005 [DC Bus Voltage]
Based on Drive Rating
1 VDC
d006 [Drive Status]
0/1 (1 = Condition True)
Bit 3
Bit 2
Bit 1
Bit 0
Decelerating
Accelerating
Forward
Running
d007-
d009
[Fault x Code]
F2/F122
F1
d010 [Process Display]
0.00/9999
0.01 – 1
d012 [Control Source]
0/9
Digit 1 = Speed Command
Digit 0 = Start Command
(See P038; 9 = “Jog Freq”)
(See P036; 9 = “Jog”)
d013 [Contrl In Status]
0/1 (1 = Input Present)
Bit 3
Bit 2
Bit 1
Bit 0
DB Trans On
Stop Input
Dir/REV In
Start/FWD In
d014 [Dig In Status]
0/1 (1 = Input Present)
Bit 3
Bit 2
Bit 1
Bit 0
Digital In 4
Digital In 3
Digital In 2
Digital In 1
d015 [Comm Status]
0/1 (1 = Condition True)
Bit 3
Bit 2
Bit 1
Bit 0
Comm Error
DSI Option
Transmitting
Receiving
d016 [Control SW Ver]
1.00/99.99
0.01
d017 [Drive Type]
1001/9999
1
d018 [Elapsed Run Time]
0/9999 Hrs
1 = 10 Hrs
d019 [Testpoint Data]
0/FFFF
1 Hex
d020 [Analog In 0-10V]
0.0/100.0%
0.1%
d021 [Analog In 4-20mA]
0.0/100.0%
0.1%
d022 [Output Power]
0.00/(Drive Power
×
2)
0.01 kW
d023 [Output Powr Fctr]
0.0/180.0 deg
0.1 deg
d024 [Drive Temp]
0/120 degC
1 degC
d025 [Counter Status]
0/9999
1
d026 [Timer Status]
0.0/9999 Secs
0.1 Secs
d028 [Stp Logic Status]
0/7
1
d029 [Torque Current]
0.00/(Drive Amps
×
2)
0.01 Amps
Smart Start-Up with Basic Program Group Parameters
= Stop drive before changing this parameter.
No.
Parameter
Min/Max
Display/Options
Default
P031 [Motor NP Volts]
20/Drive Rated Volts
1 VAC
Based on Drive Rating
Set to the motor nameplate rated volts.
P032 [Motor NP Hertz]
15/400 Hz
1 Hz
60 Hz
Set to the motor nameplate rated frequency.
P033 [Motor OL Current]
0.0/(Drive Rated Amps
×
2) 0.1 Amps
Based on Drive Rating
Set to the maximum allowable motor current.
P034 [Minimum Freq]
0.0/400.0 Hz
0.1 Hz
0.0 Hz
Sets the lowest frequency the drive will output
continuously.
P035 [Maximum Freq]
0/400 Hz
1 Hz
60 Hz
Sets the highest frequency the drive will output.
P036 [Start Source]
0/6
0 = “Keypad”
(1)
1 = “3-Wire”
2 = “2-Wire”
3 = “2-W Lvl Sens”
4 = “2-W Hi Speed”
5 = “Comm Port”
6 = “Momt FWD/REV”
0
Sets the control scheme used to start the drive.
(1)
When active, the Reverse key is also active
unless disabled by A095 [Reverse Disable].
See the PowerFlex 40 User Manual for more information on parameters.