Installing the Enhanced Field Supply Kit on 75 HP to 150 HP @ 460 VAC (40 HP to 75 HP @ 230 VAC) Drives
3-5
3.6
Replacing the Drive Fuses
Step 1. Locate the three fuses labeled 6FU, 7FU, and 8FU. See figure 3.3.
Step 2. If the fuses are different from the three provided 25 A, 600 V fuses (P/N
64676–30M), replace them with the ones provided.
Step 3. Locate the replacement fuse table on the back of the carrier. Attach one of
the adhesive fuse rating labels (P/N 179540) over each of the places
indicated in figure 3.4.
Figure 3.2 – Installing the Enhanced Field Supply Board (75 HP to 150 HP @ 460 VAC Drives)
Mounting Screws
(Qty 4)
Field Supply