3-33
GREEN
Module is online and providing data to/receiving data from application
AMBER
Module is inserted into a running system but not online. Press the Fault
Reset button on any processor module to enable the module to go online
RED
Module is ready to go online but no application is running
Channel 1 - 8
Provides an indication of the status of each input or output channel
OFF
Input module: field switch is open
Output module: output is in its de-energised state
If the run indicator is not green (the module is not reporting channel
values), all channel indicators will be off
GREEN
Input module: Channel input is on
Output module: Output is in its energised state
AMBER
Field fault
RED
Channel fault
Status Indicators on the T9110 Processor Module
Status Indicators on the T9110 Processor Module
Status Indicators on the T9110 Processor Module
Status Indicators on the T9110 Processor Module
Table 7:
Table 7:
Table 7:
Table 7:
Status Indi
Status Indi
Status Indi
Status Indicators on the 9110 Processor Module
cators on the 9110 Processor Module
cators on the 9110 Processor Module
cators on the 9110 Processor Module
Indicator
Status
Description
Healthy
Provides an indication of the module's fault status and power-
on/operational status
OFF
No power
RED
Module has a fault
Flashes RED briefly after being installed as the module is
booting up or reset is in progress
controller is off-line
GREEN
As the module is installed and receives power it flashes RED for a second
then goes GREEN as the module boots up (10 to 20 seconds).
When the module has booted up and is operational the LED stays GREEN