Document: 553632
(ICSTT-RM448_EN_P) Issue: 08:
3-17
Analogue Input Field l
Analogue Input Field l
Analogue Input Field l
Analogue Input Field loop Circuits
oop Circuits
oop Circuits
oop Circuits
These circuits can be used for simplex, dual and triple configurations of analogue input
modules. Fit a fuse (as shown) in each circuit to protect the field wiring.
Recommended Field Loop Circuits
Recommended Field Loop Circuits
Recommended Field Loop Circuits
Recommended Field Loop Circuits
Note:
A 150 ohm resistor is fitted only for the Euro Version of the Termination
Assembly (T9842 Euro Analogue Input TA, 8 ch, Simplex)
2
2
2
2----Wire Analogue Input
Wire Analogue Input
Wire Analogue Input
Wire Analogue Input
3
3
3
3----Wire Analogue Input
Wire Analogue Input
Wire Analogue Input
Wire Analogue Input