Change Parameter Setting Using RSNetWorx:
The CDN366 must be offline (not on Scanlist) to change any parameters. Some of
the parameters cannot be change, but can be read (
see CDN366 DeviceNet Specifications
for details
). Before making the parameter change, always upload the current parameters
from the CDN366 device.
1)
In the “
Parameters”
menu, double click on the parameter, and enter the new
value. Then press “Enter” to accept the new value.
2)
Click on “
Apply
” and click on “
Yes
” to download new changes to CDN366.
Another method for changing the parameters on CDN366 is using RSNetWorx.
1)
Point mouse to CDN366 icon and right click. The sub menu is prompted.
2)
Click on “
Class Instance Editor
”, and the “WARNING!” alert menu is
prompted.
3)
Click on “
Yes
” to access the class instance editor menu.
Service Code:
Used to verify or
set new/current parameters for a
single or a group of attributes.
Object Address:
Enters a
particular class, instance and
attribute to verify or change
parameter setting.
Set data in decimal or
hexadecimal value.