3-16
Programming and Parameters
Speed Command File
MO
T
O
R
CONT
R
O
L
Speed
F
eedba
ck
421
[Marker Pulse]
Latches the raw encoder count at each
marker pulse.
Default:
Min/Max:
Units:
Read Only
–/+2147483647
1
422
[Pulse In Scale]
Sets the scale factor/gain for the Pulse
Input when P423 is set to “Pulse Input.”
Calculate for the desired speed
command as follows:
Default:
Min/Max:
Units:
64
2/20000
1
423
[Encoder Z Chan]
Defines if the input wired to terminals 5 &
6 of the Encoder Terminal Block will be
used as a Pulse or Marker input. Options
1 & 3 detect a loss of signal (when using
differential inputs) regardless of the
[Feedback Select], param. 080 setting.
When option 2 or 3 is used with Profile/
Indexer mode, the “homing” routine will
position to the nearest marker pulse off of
the home limit switch.
Default:
Options:
0
0
1
2
3
“Pulse Input”
“Pulse Input”
“Pulse Check”
“Marker Input”
“Marker Check”
Fi
le
Gr
ou
p
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Relate
d
Input Pulse Rate (Hz)
Desired Cmd. (Hz)
Input Pulse Rate (Hz)
Desired Cmd. (RPM)
x
120
[Motor Poles]
for Hz, [Pulse In Scale] =
for RPM, [Pulse In Scale] =
Fil
e
Gr
ou
p
No.
Parameter Name & Description
See
for symbol descriptions
Values
Relate
d
S
PEED COMMAND
Spd Mode & Li
m
it
s
079
[Speed Units]
Selects the units to be used for all speed
related parameters. Options 0 & 1
indicate status only. Options 2 & 3 will
convert/configure the drive for that
selection.
“Convert Hz” (2) - converts all speed
based parameters to Hz, and changes
the value proportionately (i.e. 1800 RPM
= 60 Hz).
“Convert RPM” (3) - converts all speed
based parameters to RPM, and changes
the value proportionately.
Default:
Options:
0
0
1
2
3
“Hz”
“Hz”
“RPM”
“Convert Hz”
“Convert RPM”
Содержание Allen-Bradley PowerFlex 700 B Series
Страница 1: ...Adjustable Frequency AC Drive Series B Firmware Versions 4 001 User Manual www abpowerflex com ...
Страница 10: ...P 6 Overview Notes ...
Страница 36: ...1 26 Installation Wiring Notes ...
Страница 118: ...3 78 Programming and Parameters Notes ...
Страница 162: ...A 28 Supplemental Drive Information Notes ...
Страница 227: ......