Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
87
Chapter 5 Preventative Maintenance and Component Replacement
Isolation Transformer
Cabinet
Replace/Clean Door-mounted Air Filters
Periodically remove and clean, or remove and replace, the air filters according
to the Preventative Maintenance table on
. The frequency with which
you renew the filters depends on the cleanliness of the available cooling air.
There are two types of design for the air filters. The air filters are located on the
Power Module cabinet and the Isolation Transformer cabinet. The quantity of
air filters on the cabinet door are different, depending on the drive ratings.
However, the method to remove or clean the air filters is the same. The screens
may be replaced while the drive is operating, but the procedure is easier to
perform while the drive is shut down.
If the drive is running, you must replace the filter as soon as possible to
prevent foreign material from entering into the drive.
Recommended Cleaning Method of Filters:
•
Vacuum Cleaner – A vacuum cleaner on the inlet side of the filter will
remove accumulated dust and dirt.
•
Blow with Compressed Air – Point compressed air nozzle in opposite
direction of operating airflow (Blow from exhaust side toward intake
side)
•
Cold Water Rinse – Under normal conditions the foam media used in the
filters, require no oily adhesives. Collected dirt is washed away quickly
and easily using just a standard hose nozzle with plain water.
•
Immersion in Warm Soapy Water – Where stubborn air-borne dirt is
present, the filter may be dipped in a solution of warm water and mild
detergent. Rinse in clear clean water, let stand until completely dry and
free of moisture.
Use only Rockwell Automation-supplied or -approved replacement filters.
Replace the filters in the reverse order of its removal. Check that there are no
openings to allow foreign matter to enter the drive.
Replace/Clean Door-mounted Air Filters
Inspect Top Mounted Cooling Fans
Replace Top Mounted Cooling Fans
Inspect Door Position Limit Switch
Replace Door Position Limit Switch
ATTENTION:
Wait at least 15 minutes for the stored energy to fully discharge
before performing maintenance on the Isolation Transformer cabinet. Failure
to do so may result in severe burns, injury, or death.
ATTENTION:
The filter must be completely dry before reinstalling.
Содержание Allen-Bradley PowerFlex 6000
Страница 10: ...10 Rockwell Automation Publication 6000 UM002G EN P August 2022 Preface Notes ...
Страница 82: ...82 Rockwell Automation Publication 6000 UM002G EN P August 2022 Chapter 4 Parameters and Function Codes Notes ...
Страница 134: ...134 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix C Preventative Maintenance Schedule Notes ...
Страница 136: ...136 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix D Torque Requirements Notes ...
Страница 148: ...148 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix E Spare Parts Storage Notes ...