Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
Appendix C Preventative Maintenance Schedule
ATTENTION:
Customers can replace components for the PowerFlex 6000
drives. However repairs must only be performed by qualified Rockwell
Automation personnel.
Table 11 - Preventative Maintenance Schedule (0…10 yrs.)
Interval Period (in years from commissioning date)
0
1
2
3
4
5
6
7
8
9
10
Component
Location
Component
Category
Component/Item
Isolation
Transformer
Cabinet
Air-cooling System
Door -mounted Air Filters
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
Top-mounted Cooling
Fans
I
I
I
I
RFB/R
I
I
I
I
RFB/R
Integral Magnetics Isolation Transformer
I
I
I
I
I
I
I
I
I
I
LV Control
Isolation Transformer
Temperature Monitor
I
I
I
I
I
I
I
I
I
I
Voltage Sensing Board
I
I
I
I
I
I
I
I
I
I
Power Module
Cabinet
Air-cooling System
Door -mounted Air Filters
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
C / R
Top-mounted Cooling
Fans
I
I
I
I
RFB/R
I
I
I
I
RFB/R
Power Module
Electrolytic Capacitors
(1)
I
I
I
I
I
I
I
I
I
I
Misc.
HECS
I
I
I
I
I
I
I
I
I
I
LV
Control
Cabinet
Misc.
AC/DC Power Supplies
I
I
I
I
I
I
I
I
I
I
UPS
UPS
(2)
I
I
I
I
I
I
I
I
I
I
LV Control
PLC
I
I
I
I
I
I
I
I
I
I
Control Unit
I
I
I
I
I
I
I
I
I
I
HMI
I
I
I
I
I
I
I
I
I
I
LV Control Relays
I
I
I
I
I
I
I
I
I
I
LV Control Circuit
Breakers
I
I
I
I
I
I
I
I
I
I
All
Connections
LV Component Terminal &
Plug-in Connections
I
I
I
I
I
I
I
I
I
I
Medium Voltage Cable
Connections
I
I
I
I
I
I
I
I
I
I
Transformer Secondary
Winding Connections
I
I
I
I
I
I
I
I
I
I
Power Module Input and
Output Power
Connections
I
I
I
I
I
I
I
I
I
I
General
Enhancements
Firmware
—
—
Rv
—
—
Rv
—
—
Rv
Rv
Hardware
—
—
Rv
—
—
Rv
—
—
Rv
—
Operational
Conditions
Parameters / Variables
I
I
Rv
I
I
Rv
I
I
Rv
I
Spare Parts
Inventory Needs
I
I
Rv
I
I
Rv
I
I
Rv
I
(1) Based on full load/full speed operation at 8700 hours per year at 30 °C (86 °F) ambient temperature. For higher ambient temperatures the replacement should be done sooner, contact
factory for details.
(2) Fully discharge and recharge the UPS batteries every 6 months, to extend battery life.
Содержание Allen-Bradley PowerFlex 6000
Страница 10: ...10 Rockwell Automation Publication 6000 UM002G EN P August 2022 Preface Notes ...
Страница 82: ...82 Rockwell Automation Publication 6000 UM002G EN P August 2022 Chapter 4 Parameters and Function Codes Notes ...
Страница 134: ...134 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix C Preventative Maintenance Schedule Notes ...
Страница 136: ...136 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix D Torque Requirements Notes ...
Страница 148: ...148 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix E Spare Parts Storage Notes ...