![Rockwell Automation Allen-Bradley PowerFlex 4 Скачать руководство пользователя страница 84](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-4/allen-bradley-powerflex-4_user-manual_1475422084.webp)
C-2
RS485 (DSI) Protocol
Control Terminal 16 on the PowerFlex 4 must also be connected to PE
ground (there are two PE terminals on the drive). See
more information.
Parameter Configuration
The following PowerFlex 4 parameters are used to configure the drive to
operate on a network.
Supported Modbus Function Codes
The peripheral interface (DSI) used on PowerFlex 4 drives supports
some of the Modbus function codes.
Important:
Modbus devices can be 0-based (registers are numbered
starting at 0) or 1-based (registers are numbered starting at
1). Depending on the Modbus Master used, the register
addresses listed on the following pages may need to be
offset by +1. For example, Logic Command may be register
address 8192 for some master devices (e.g. ProSoft
3150-MCM SLC Modbus scanner) and 8193 for others
(e.g. PanelViews).
Parameter
Details
Reference
P036 [Start Source]
Set to 5 “RS485 (DSI) Port” if Start is controlled from
the network.
P038 [Speed Reference]
Set to 5 “RS485 (DSI) Port” if the Speed Reference is
controlled from the network.
A103 [Comm Data Rate]
Sets the data rate for the RS485 (DSI) Port. All nodes
on the network must be set to the same data rate.
A104 [Comm Node Addr]
Sets the node address for the drive on the network.
Each device on the network requires a unique node
address.
A105 [Comm Loss Action] Selects the drive’s response to communication
problems.
A106 [Comm Loss Time]
Sets the time that the drive will remain in
communication loss before the drive implements A105
[Comm Loss Action].
A107 [Comm Format]
Sets the transmission mode, data bits, parity and stop
bits for the RS485 (DSI) Port. All nodes on the network
must be set to the same setting.
Modbus Function Code
Command
03
Read Holding Registers
06
Preset (Write) Single Register
userman.book Page 2 Friday, June 21, 2002 2:48 PM
Содержание Allen-Bradley PowerFlex 4
Страница 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Страница 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Страница 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Страница 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Страница 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...