Programming and Parameters
3-23
Advanced Program Group
(continued)
Stop drive before changing this parameter.
A100 [Fault Clear]
Resets a fault and clears the fault queue.
Options
0
“Ready” (Default)
1
“Reset Active Fault”
2
“Clear Fault Queue”
(Parameters d007-d009
A101 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options
0
“Unlocked” (Default)
1
“Locked”
A102 [Testpoint Sel]
Used by Rockwell Automation field service personnel.
Values
Default
400
Min/Max:
0/FFFF
Display:
1 Hex
A103 [Comm Data Rate]
Sets the serial port rate for the RS485 (DSI) port.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Options
0
“1200”
1
“2400”
2
“4800”
3
“9600” (Default)
4
“19.2K”
5
“38.4K”
A104 [Comm Node Addr]
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Values
Default
100
Min/Max:
1/247
Display:
1
userman.book Page 23 Friday, June 21, 2002 2:48 PM
Содержание Allen-Bradley PowerFlex 4
Страница 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Страница 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Страница 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Страница 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Страница 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...