Installation/Wiring
1-17
The drive speed command can be obtained from a number of different
sources. The source is normally determined by P038
However, when A051 or A052
is set to option 2, 4, 5 or
6, and the digital input is active, A051 or A052 will override the speed
reference commanded by P038
for the override priority.
Start and Speed Reference Control
Jog Input
Enabled and Active:
A051 or A052 = 2
Yes
Drive will Start and Run at Jog Speed.
Direction comes from
Terminal 03 Dir/Run REV
Local/Remote Input
Enabled and Active:
A051 or A052 = 5
Yes
Start, Speed and Direction commands
come from Integral Keypad.
Comm Select Input
Enabled and Active:
A051 or A052 = 6
Yes
Start, Speed and Direction commands
come from RS485 (DSI) port.
P038 [Speed Reference]
= 4 or 5
Yes
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
A051 / A052
Preset Inputs Active
Yes
Run as specified by
A071-A073 [Preset Freq 1-3].
Start and Direction commands come
from P036 [Start Source].
No
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
No
No
No
No
userman.book Page 17 Friday, June 21, 2002 2:48 PM
Содержание Allen-Bradley PowerFlex 4
Страница 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Страница 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Страница 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Страница 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Страница 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Страница 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Страница 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...