Kinetix 350 Single-axis EtherNet/IP Servo Drives
5
Rockwell Automation Publication 2097-IN008F-EN-P - September 2015
Install the Kinetix 350 Drive
These procedures assume that you have prepared your panel, and understand how to bond your
system. For installation instructions regarding equipment and accessories that are not included
here, refer to the instructions that came with those products.
Mount the Kinetix 350 Drive
Follow these steps to mount the drive.
1.
Observe these clearance requirements when mounting the drive to the panel.
SHOCK HAZARD:
To avoid hazard of electrical shock, mount and wire of the Kinetix 350 drive
before you apply power. Once power is applied, connector terminals can have voltage present even
when not in use.
ATTENTION:
Plan the installation of your system so that you can cut, drill, tap, and weld with the
system removed from the enclosure. Because the system is open-type construction, be careful to
keep any metal debris from falling into it. Metal debris or other foreign matter can become lodged
in the circuitry and result in damage to components.
IMPORTANT
Mount the module in an upright position as shown. Do not mount the module on
its side.
Drive
Cat. No.
Dimensions A
mm (in.)
2097-V31PR0-LM
185 (7.29)
2097-V31PR2-LM
2097-V32PR0-LM
230 (9.04)
2097-V32PR2-LM
2097-V32PR4-LM
2097-V33PR1-LM
185 (7.29)
(1)
(1)
If you are using an AC line filter, add
50 mm (2 in.).
2097-V33PR3-LM
2097-V33PR5-LM
2097-V33PR6-LM
230 (9.04)
2097-V34PR3-LM
2097-V34PR5-LM
2097-V34PR6-LM
230 (9.04)
A
•
More clearance and different hole patterns are required for side mount
and rear mount AC line filters. See the table and
for more details.
•
More clearance is required depending on the other accessory items
installed.
•
More clearance is required for the cable and wires that are connected to
the top, front, and bottom of the drive.
•
An extra 150 mm (6.0 in.) is required when the drive is mounted near
noise sensitive equipment or clean wire ways.
for Kinetix 350 drive dimensions.
25 mm (1.0 in.) Clearance
for Airflow and Installation
25 mm (1.0 in.) Clearance
for Airflow and Installation
3 mm (0.12 in.)
Side Clearance
3 mm (0.12 in.)
Side Clearance