Ground Your Kinetix 350 Drive to the Subpanel
If the Kinetix 350 drive is mounted on a painted subpanel, ground to a bonded cabinet ground
bus with a braided ground strap or 4.0 mm
2
(12 AWG) solid-copper wire, 100 mm (3.9 in.) long.
Connect the Braided Ground Strap
For dimensions, see
Kinetix 350 Drive Mounting Dimensions
.
ATTENTION:
To avoid personal injury and equipment damage, verify the following:
•
Installation complies with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline
provisions for safely installing electrical equipment.
•
Motor power connectors are used only for connection purposes. Do not use motor power
connectors to turn the unit on and off.
•
Shielded power cables are grounded to prevent potentially high voltages on the shield.
Bonded Cabinet
Ground Bus
Ground Grid or Power
Distribution Ground
Braided
Ground Strap
Ground Stud