20

Rockwell Automation Publication 440L-IN012A-EN-P - November 2017

GuardShield Type 4 and GuardShield Remote Teach

Switch on the GuardShield light curtain and check its function by 

observing the following:

Safety Instructions—Maintenance

For safety reasons, all inspection results are recorded. 
Only persons, who clearly understand the functioning of the 

GuardShield light curtain and of the machine, can conduct an 

inspection.
If the installer, planning engineer, and operator are different people, 

make sure that they have sufficient information available to conduct the 

inspection. 

Daily Inspection

Operate the machine and check, if the hazardous movement stops under 

the following circumstances.

Figure 44 - Proper Testing of Protective Field Using Test Rod

Six-month Inspection

Check the following items every six months or whenever a machine 

setting was changed.

Cleaning

If the optic front cover of the GuardShield light curtain is dirty, the 

outputs of the GuardShield light curtain turn off. Take a clean, soft 

cloth and rub without pressure. Do not apply aggressive, abrasive, or 

gritty cleaning agents, which can attack the surface.

Date Code

Figure 45 - Product Label for Units Produced before 2017

Items that are marked in 

Figure 45

:

• Serial number
• Production data code

Use the codes in 

Table 46

 for older GuardShield light curtain units that 

don’t have the date printed on the label.

5.

The OSSD outputs are not connected to +24V DC.

6.

The connected switching elements (load) are not connected to 24V DC. 

7.

No connection to a conventional power supply.

8.

If two or more GuardShield light curtain are to be used, make sure that each system is 

properly installed, to avoid optical interference.

9.

Two seconds after switching on, the system starts to work properly, if the protective field is 

free of obstructions.

ATTENTION: 

Never operate the GuardShield light curtain before 

conducting the following inspection. Improper inspection can lead 
to serious or even deadly injury.

1.

Approach to hazardous machine parts must only be possible through passage through the 

protective field of GuardShield light curtain.

2.

Operators cannot step through the sensing area while working on dangerous machine 

parts.

3.

The safety distance of the application is bigger than the calculated value. 

4.

The optic front cover is not scratched or dirty.

5.

The protective field is interrupted. 

6.

The hazardous movement stops immediately if you interrupt the protective field by placing 

the test rod directly: 

• In front of the transmitter

• In front of the receiver

• In between the transmitter and receiver

7.

No hazardous machine movement while the test rod is anywhere within the protective 

field.

8.

The power supply of the GuardShield light curtain is turned off. 

9.

If the blanking function is activated, check all sections of the protective field with the 

appropriate test rod (see 

Figure 44 on page 20

).

IMPORTANT

If any of the conditions previously described do not result in 

the hazardous motion of the machine stopping, do not allow 

the protected machine to be placed in operation.

1.

Machine stops or does not obstruct any safety function.

2.

The latest machine or connection modifications have no effect on the control system.

3.

The outputs of the GuardShield light curtain are properly connected to the machine.

4.

The total response time of the machine is shorter than the calculated value.

5.

Cables and plugs of the GuardShield light curtain are in flawless condition.

6.

Mounting brackets, caps and cables are tightly secured.

Tr

ansmitt

er

Rec

eiv

er

Rockwell Automation Inc., 1201 South 2nd Street Milwaukee, WI 53204, USA

GuardShield

TM

SER

Power Consumption

Supply Voltage

Safety Parameters

Electro-Sensive

Protecve Equip.

19KP

EN62061/ IEC61508

Operating Instructions

Degree of Protection

Q

Range

Protective Height

Response Time with Coding

Response Time w/out Coding

PLANT 1150

DATE 1705

PRODUCT OF MEXICO

SN

REV

CAT

MAT NO

Ambient Temp.

A

D

1234567890

IEC61489/ EN ISO 13849

N_GRAPHIC1

N_CE

N_CTICK

N_WEEE

N_GRAPHIC_ROHS

N_UL

F

G

H

J

L

O

P

Содержание Allen-Bradley Guardmaster GuardShield Remote Teach

Страница 1: ...nt of operation and perimeter and access detection It is a self contained two box Type 4 electro sensitive protective equipment ESPE with DIP switch selectable operating modes The GuardShield light cu...

Страница 2: ...e is a Type 4 ESPE as defined by IEC 61496 1 and IEC 61496 2 Therefore it is allowed for use with controls In safety Cat 4 up to PLe in accordance with EN ISO 13849 1 SIL CL3 in accordance with EN 620...

Страница 3: ...ation removes the possibility of operation by a person working inside the hazardous area The statutory and local rules and regulations must be observed when installing and using the device Restart int...

Страница 4: ...segments The individual segments can have mixed resolutions for instance 14 mm and 30 mm 1 18 in as long as the pairs have the same protective heights and resolutions Cascade segments can be used as...

Страница 5: ...eration is through DIP switch setting in the GuardShield light curtain receiver see Table 37 on page 17 EDM is not available in the middle and end segments of a cascading GuardShield light curtain sys...

Страница 6: ...d activated FloatingBlanking The floating blanking mode of operation is activated through DIP switch settings that are located in the GuardShield light curtain receiver see Receiver Factory Settings o...

Страница 7: ...ing Blanking Symbol Description Beam not interrupted Beam interrupted Beamisactivated forFixedBlanking andnot interrupted Beamisactivated forFixedBlanking andinterrupted Case 1 2 3 4 5 6 7 8 Infrared...

Страница 8: ...ime that is measured at approximately the 90 position of the crankshaft rotation Resolution Protective Height Number of Beams ResponseTime w o Coding ResponseTime w Coding 14 0 55 160 6 3 16 20 ms 30...

Страница 9: ...object sensitivity of the safety light curtain Object sensitivity resolution is the smallest diameter object which is detected anywhere in the sensing field Example for US In a perpendicular safety l...

Страница 10: ...between sender and receiver Figure 12 Minimum Distance from Reflecting Surfaces Howto DeterminetheMinimumDistancefromtheReflecting Surfaces Determine the distance D m sender receiver Read the minimum...

Страница 11: ...L ALAT and mounting bracket 450L ALAT C is offered as an accessory for aligning the GuardShield light curtain without Integrated Laser Alignment see Laser Alignment Tool on page 35 AlignmentProceduref...

Страница 12: ...ective solution is to interconnect an additional light curtain in series to the vertical pair Select a Host or cascade pair of GuardShield safety light curtains with a protective height and resolution...

Страница 13: ...ry to use additional brackets see Figure 23 to mount the GuardShield light curtain at a proper safety distancefromthe machinery hazard Forapplications with shock and or vibrations also see Table 66 Fi...

Страница 14: ...Low Voltage Directives The grounded conductor of the power supply device must be connected to a grounded conductor PE The maximum deviation of the voltage levels is 24V DC 20 EDMConnection See Relay...

Страница 15: ...ter Brown 1 24V DC White 2 No Connection Blue 3 0VDC Black 4 MachineTestSignal Receiver Connection Face View of Female DC Micro Color PinNo Signal Receiver White 1 Auxiliary Output Brown 2 24V DC Gree...

Страница 16: ...le IMPORTANT IfMPCE EDMisactivated intheGuardShieldlightcurtain the application requires asafety contactor If MPCE EDMis not used K1 K2 can bestandardcontactors M 24V DC 24V Ground SENDER OSSD 1 OSSD...

Страница 17: ...ton Switch Switch Function Default Setting Description 1 Mode Activation Combination activates oneofthe followingmodes Guardonly startinterlock restart interlock ON Guard Only see Table 39 on page17 2...

Страница 18: ...tep 2 Selectthe desiredDIPswitch setting Step 3 Press and hold theTeach button Theyellow status indicator startsflashing at 10 Hz 10x per second RX Blanking indicator TX Emitting indicator Step 4 Afte...

Страница 19: ...set mode in start orrestart interlock aligned 5 Fixed blankingmode aligned not ininterlock 6 FloatingorFloating Fixed Blanking mode aligned not in interlock 7 Transmitter testinputactive pin 4 8 Inter...

Страница 20: ...llowinginspection Improperinspectioncanlead to serious or even deadly injury 1 Approach to hazardous machineparts mustonly bepossiblethrough passagethrough the protectivefield ofGuardShieldlight curta...

Страница 21: ...XX M or4K R 02 M representedManchester NH replacedby 4KforMonterrey Mexico J 2004 K 2005 L 2006 M 2007 N 2008 P 2009 R 2010 S 2011 T 2010 U 2013 V 2014 W 2015 Y 2016 Z 2017 Rockwell Automation Inc 12...

Страница 22: ...ON state OSSDOFF state Blanking Alignment Interlock Constant ON whenOSSDis in ON state greenindicator Constant ON whenOSSDis in OFF state redindicator Lights upatinterruptionofprotective fieldor if f...

Страница 23: ...itter Receiver Resolution mm in No of Beams Protective Heights mm in PairWeight kg lb Finger Resolution 440L P4JL0320YD 440L T4JL0320YD 440L R4JL0320YD 14 0 55 32 320 12 59 5 17 2 35 440L P4JL0480YD 4...

Страница 24: ...35 440L C4J0480YD 440L G4J0480YD 440L F4J0480YD 14 0 55 48 480 18 89 6 59 2 99 440L C4J0640YD 440L G4J0640YD 440L F4J0640YD 14 0 55 64 640 25 19 7 99 3 62 440L C4J0800YD 440L G4J0800YD 440L F4J0800YD...

Страница 25: ...8 80 1600 62 99 19 28 8 75 Sensor Pair Transmitter Receiver Resolution mm in No of Beams Protective Heights mm in Pair Weight kg lbs Finger Resolution 440L C4JL0320YA 440L G4JL0320YA 440L F4JL0320YA 1...

Страница 26: ...ransmitter R Receiver Standard C Host Pair G Host Transmitter F Host Receiver Cascading Bulletin Number 0160 Protective Height 0320 0480 0960 1440 0640 1120 1600 0800 1280 1760 R Remote Teach Pigtail...

Страница 27: ...28 5 632 1 5 24 9 0 06 440L 4 0640Y 640 0 5 25 2 0 02 756 29 8 792 1 5 31 2 0 06 440L 4 0800Y 800 0 6 31 5 0 02 916 36 1 952 1 5 37 5 0 06 440L 4 0960Y 960 0 6 37 8 0 02 1076 42 4 1112 1 5 43 8 0 06...

Страница 28: ...9 686 26 6 712 28 0 440L 1 4 2 L0640Y 3 640 25 2 836 32 9 872 34 3 440L 1 4 2 L0800Y 3 800 31 5 996 39 2 103 4 1 440L 1 4 2 L0960Y 3 960 37 8 1156 45 5 119 4 7 440L 1 4 2 L1120Y 3 1120 44 1 1316 51 8...

Страница 29: ...supplied with each GuardShield Remote Teach light curtain receiver The GuardShield Remote Teach Box light curtain system consists of Remote teach key selector switch box with mounting plate and two k...

Страница 30: ...vation and configuration of a monitored fixed blanked area within the GuardShield light curtain protective height Make any additional DIP switch settings now RemoteTeachProcedure 1 Position object in...

Страница 31: ...stem 1600 mm 63 in protectiveheight 30 mm 1 18 in resolution 440L S4K1760YR GuardShield RemoteTeachlight curtain system 1760 mm 69 3 in protectiveheight 30 mm 1 18 in resolution Catalog Number Descrip...

Страница 32: ...GWS0800 440L AGWS0960 440L AGWS1120 440L AGWS1280 440L AGWS1440 440L AGWS1600 440L AGWS1760 GuardShield light curtainTest Rod 14 mm 450L AT 14 GuardShield light curtainTest Rod 30 mm 450L AT 30 GuardS...

Страница 33: ...0 mm 70 86 in 15 m 49 21 ft 1896 1840 1872 1940 8 x 13 50 1 96 73 2 87 A Ls L B A A Section A A 120 114 4 48 13 3 5 24 35 1 37 54 2 12 44 4 1 74 75 2 95 2 5 0 09 6 5 0 25 4 5 0 17 10 5 0 41 Model No S...

Страница 34: ...40L P2K 0480YD 440L P4A2500YD 440L AM0750600 440L AM1250600 440L P4 0640Y 440L P2K 0640YD 440L AM0750750 440L AM1250750 440L P4 0800Y 440L P2K 0800YD 440L AM0750900 440L AM1250900 440L P4 0960Y 440L P...

Страница 35: ...GuardShield light curtain transmitter host patchcord has 4 pin DC micro over molded quick disconnect connectors that are offered in lengths of 0 3 m 0 98 ft 1 m 3 28 ft and 2 m 6 56 ft The GuardShiel...

Страница 36: ...CDM 1 5 pin M12 patchcord 1 3 28 5 6 7 8 4 3 1 2 889D F5ACDM 2 5 pin M12 patchcord 2 6 56 889D F5ACDM 5 5 pin M12 patchcord 5 16 4 889D F5ACDM 10 5 pin M12 patchcord 10 32 81 IMPORTANT Transmitter and...

Страница 37: ...o and including SIL cl3 in accordance with EN 61508 and EN 62061 Performance Level e and Category 4 in accordance with ISO 13849 1 ESPE Type 4 safety light curtain in accordance with EN IEC 61496 Comp...

Страница 38: ...38 Rockwell Automation Publication 440L IN012A EN P November 2017 GuardShieldType 4and GuardShield RemoteTeach Notes...

Страница 39: ...Rockwell Automation Publication 440L IN012A EN P November 2017 39 GuardShieldType 4andGuardShield RemoteTeach Notes...

Страница 40: ...ent complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center KnowledgebaseArticles How toVideos FAQs...

Отзывы: