![Rockwell Automation Allen-Bradley G Series Скачать руководство пользователя страница 45](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-g-series/allen-bradley-g-series_user-manual_1475408045.webp)
Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
45
Chapter 4 Maintenance
7. Using a 5/16 in. socket, remove the #10-32 hardware holding the stainless
steel guide/stop plate in place, and then remove the guide/stop plate
(
). The contactor not shown for clarity.
Figure 35 - Removal of Guide/Stop Plate
8. Remove the flapper by sliding it to the right until it stops and then
pulling it towards the front of the contact (
). The trip (magnet)
coil and coil core are now exposed (The contactor not shown for clarity).
Figure 36 - Removal of Flapper
9. Remove the coil core (
) and trip (magnet) coil using a right angle
Allen key. The contactor is not shown for clarity.
Figure 37 - Trip Coil and Core Removal
10. Slide the coil core from the trip (magnet) coil and then place the
replacement coil onto the coil core.
Guide/Stop Plate
#10-32 Hardware
Flapper
Step 1:
Slide Flapper to Right.
Step 2:
Pull Flapper Forward
to Remove
Magnet Coil
Coil Core
Use Right Angle
Allen Key
Содержание Allen-Bradley G Series
Страница 1: ...Medium Voltage 450 A Contactor Series G Bulletin Number 1502 User Manual Original Instructions ...
Страница 6: ...6 Rockwell Automation Publication 1502 UM060A EN P October 2020 Notes ...
Страница 16: ...16 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 1 Product Description Notes ...
Страница 20: ...20 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 2 Receiving and Handling Notes ...
Страница 48: ...48 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 4 Maintenance Notes ...
Страница 50: ...50 Rockwell Automation Publication 1502 UM060A EN P October 2020 Chapter 5 Troubleshooting Notes ...