44
Rockwell Automation Publication 1502-UM060A-EN-P - October 2020
Chapter 4 Maintenance
Figure 32 - Auxiliary Contact Assembly Removal
4. Disconnect the mechanical latch trip coil leads form the auxiliary contact
assembly using a Phillips screwdriver.
5. Using a 3/8 in. socket, remove the ¼-20 hardware holding the mechanical
trip mechanism in place, and then remove the mechanical trip
mechanism (
).
Figure 33 - Removal of Mechanical Trip Mechanism
6. Remove the “E” clip and washer from the latch lever assembly shaft and
then remove the shaft (
). Remove the latch lever assembly from
the mechanical latch base. The return spring is “seated” on the right side
of the mechanical latch base (the contactor is not shown for clarity).
Figure 34 - Removal of Latch Lever Assembly
Auxiliary Contact
Assembly
Retaining Bolt
Mechanical Trip
Mechanism
1/4-20 Hardware
(Qty. 2)
Contactor
Latch Lever Assembly
“E” Clip and Washer
Return Spring Seat
Shaft