Rockwell Automation Publication CC-QS027D-EN-P - August 2015
33
Validate Your System
Chapter 2
Review the System Overview
The PanelView 800 graphic terminal can be connected to the Micro800 controller with a CIP serial or CIP on Ethernet
connection:
• When a CIP serial connection is used, connect the PanelView 800 terminal to the Micro800 controller's embedded
serial port by using a 1761-CBL-PM02 cable.
• When a CIP on Ethernet connection is used, connect the PanelView 800 terminal to the Ethernet switch and
connect the Ethernet switch to the Micro800 controller’s embedded Ethernet port by using Ethernet patchcords.
Both methods of connection are explained in this manual, but choose only one method for your project.
The 900-TC temperature controller is connected to the Micro800 controller’s Isolated Serial Port plug-in module (catalog
number 2080-SERIALISOL) with two-wire, twisted-pair shielded cable (Belden 3105A recommended) and one
900-TC
xxx
COM card per 900-TC temperature controller. These devices communicate with the Modbus RTU protocol
(RS-485). The Micro800 controller is the Modbus master, and the 900-TC temperature controller is the Modbus slave.
Additional Modbus RTU slave devices can be daisy-chained on this RS-485 network.
Figure 2 - Device and Network Layout Diagram
PanelView
Component
Micro800
900-TC
Temperature
Controller
Other
Modbus Devices
1761-CBL-PM02 (CIP serial) Cable
or
Ethernet Switch and Cables
2080-SERIALISOL
RS-485 (Belden 3105A) Cable to
900-TC
xxx
COM card
Содержание Allen-Bradley 900-TC
Страница 1: ...900 TC Temperature Control Device Building Block Connected Components Accelerator Toolkit Quick Start ...
Страница 4: ...4 Rockwell Automation Publication CC QS027D EN P August 2015 Where to Start Notes ...
Страница 10: ...10 Rockwell Automation Publication CC QS027D EN P August 2015 Preface Notes ...
Страница 50: ...50 Rockwell Automation Publication CC QS027D EN P August 2015 Chapter 2 Validate Your System Notes ...
Страница 59: ......