Rockwell Automation Publication CC-QS027D-EN-P - August 2015
23
900-TC Temperature Controller Setup
Chapter 1
13. Press Enter on your personal computer keyboard.
The value appears in the Read field.
14. Use the Up and Down arrows on the main dialog box to access other communication parameters shown in the table
below.
15. Repeat
step 11
and
step 12
to set the following communication parameters for your application.
The software does not list individual values but uses digits as shown in the table.
Proceed to the next section to set other parameters used in this application.
Parameter
Setting
[131] Protocol Setting
1
MoD
[132] Communications Unit No.
1
Change to your specific node address. Node address 1 is the default setting.
[133] Communications Baud Rate
4
19.2 Kbps
[136] Communications Parity
0
None
[137] Send Data Wait Time
0…99
20 ms (default)