Rockwell Automation Allen-Bradley 193-DNENCAT Скачать руководство пользователя страница 21

Rockwell Automation Publication 193-UM014A-EN-P - July 2011

21

        

Chapter

 

2

From the EDS File Download Site

The EDS file for the EtherNet/IP Communications Auxilliary can also be 
downloaded from the Allen-Bradley EDS File download site.  Using a web 
browser on the personal computer that is connected to the internet, a user can 
download the EDS file by following these steps:

1.

Type http://www.ab.com/networks/eds on the address line of the web 
browser.

2.

Select the network type as EtherNet/IP and click Search.

3.

Locate the EDS file for the EtherNet/IP Communications Auxiliary and 
download it to the personal computer.

Register the EDS File

After the EDS file has been downloaded, a user will need to register the EDS file 
with the software that configures the EtherNet/IP network.  The following 
example lists the steps needed to register an EDS file with Rockwell Automation’s 
RSLinx Classic software.

Содержание Allen-Bradley 193-DNENCAT

Страница 1: ...User Manual Bulletin 193 EtherNet IP Communications Auxiliary Catalog Number 193 DNENCAT 193 DNENCATR...

Страница 2: ...ility is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part w...

Страница 3: ...HAZARD To prevent electrical shock disconnect the EtherNet IP Communications Auxilliary from its power source before installing or servicing Install in suitable enclosure Keep free from contaminants...

Страница 4: ...ay result in malfunction of the product ATTENTION Only personnel familiar with the EtherNet IP Communications Auxilliary and associated machinery should plan to install set up and maintain the system...

Страница 5: ...ally and requires 37 4 mm 1 1 2 in of clearance at the top and bottom to allow for proper air flow The temperature ratings for the unit will be derated if not mounted in this manner Front View Module...

Страница 6: ...recommended The EtherNet IP Communications Auxilliary complies with the Open Device Vendors Association ODVA DeviceNet compliance testing when used with 60 m or less of trunk cable with 60 or fewer n...

Страница 7: ...s Figure 4 Dimension Diagram ATTENTION Use a shielded DeviceNet cable to comply with CISPR 22 and CISPR 24 DNET Black 24V CAN L Blue Shield CAN H White DNET Red 24V Earth Ground 5 85 0 23 105 0 4 13 1...

Страница 8: ...n Devices RJ45 Network Media Both the 193 DNENCAT and 193 DNENCATR devices support a Star EtherNet topology in which all EtherNet nodes wire back to a central EtherNet switch hub or router as shown in...

Страница 9: ...er 1 Figure 6 Ring EtherNet Topology The Cat No 193 DNENCATR supports Rockwell Automation s Device Level Ring DLR topology as a slave device in which the EtherNet IP network will still continue to com...

Страница 10: ...10 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 1...

Страница 11: ...ach xxx is a number from 0 255 Do not use the following IP addresses as these are reserved values 0 0 0 1 0 255 255 255 127 0 0 0 127 255 255 255 224 255 255 255 255 255 255 255 Subnet Mask Subnet add...

Страница 12: ...lliary comes with three node address selection switches which allow the user to select the last octet for the IP address 192 168 1 xxx Network Parameter Description Host Name A host name is part of a...

Страница 13: ...the Start menu This utility recognizes DHCP enabled devices and provides an interface to configure a static IP address for each device To assign network parameters via the BOOTP DHCP utility perform...

Страница 14: ...server addresses and domain name 4 Click OK The Request History panel displays the hardware addresses of modules issuing BOOTP or DHCP requests 5 Double click the MAC address of the module to be conf...

Страница 15: ...power cycle the module clears the current IP configuration and will again begin sending DHCP requests Assign Network Parameters Via a Web Browser MAC Scanner Software In the event that a user does no...

Страница 16: ...gned to the MAC ID of the EtherNet IP Communications Auxilliary The IP address will have a format that is similar to 192 168 0 100 7 Open a web browser and type the IP address on the address line to v...

Страница 17: ...for the user name leave the password field blank then click OK 10 Assign the appropriate network settings per the recommendation of the network administrator for the network that this module will be c...

Страница 18: ...to retain its static address before reconnecting to the uplink This is not a problem if you have node names configured in the module and leave DHCP enabled Duplicate IP Address Detection When you cha...

Страница 19: ...ses ElectronicDataSheet EDS File Installation Before the EtherNet IP Communications Auxilliary is configured to communicate on an EtherNet IP network it must be registered to the software that configu...

Страница 20: ...dule After the IP address for the module has been configured connect the module to same EtherNet network as a personal computer Using a web browser on the personal computer a user can download the EDS...

Страница 21: ...following these steps 1 Type http www ab com networks eds on the address line of the web browser 2 Select the network type as EtherNet IP and click Search 3 Locate the EDS file for the EtherNet IP Co...

Страница 22: ...apter 2 1 Start the EDS Hardware Installation Tool located at Start Programs Rockwell Software RSLinx Tools 2 Select Add to register a new device 3 Select the Register a single file radio button then...

Страница 23: ...Rockwell Automation Publication 193 UM014A EN P July 2011 23 Chapter 2 4 Click Next to accept the installation test results 5 Click Next to accept the graphic image...

Страница 24: ...24 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 2 6 Click Next to register the device 7 Click Finish to successfully register the module...

Страница 25: ...purpose of this chapter is to assist in configuring the DeviceNet Network with the EtherNet IP Communications Auxilliary A DeviceNet network can be configured using the internal web interface from th...

Страница 26: ...ytes 4 If needed adjust DNet IO Request Packet Interval RPI and DNet IO Inhibit DNet IO RPI determines the time it takes for data to be requested DNet IO Inhibit is the time used on DeviceNet Change o...

Страница 27: ...Scan List to change the DeviceNet node address of the EtherNet IP Communcations Auxilliary 6 Change the DeviceNet network address to the appropriate node address then click Save 7 Click OK to finish...

Страница 28: ...28 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 3...

Страница 29: ...ta Gaps between addresses are acceptable and have no effect on system performance If the final layout of the system is not certain at this time leave gaps between addresses to allow flexibility as the...

Страница 30: ...Literature Library at www rockwellautomation com literature Set the Node Address Using the Hardware Mechanism Many DeviceNet devices feature a hardware mechanism to set the network node address e g a...

Страница 31: ...lict with duplicate node addresses due largely in part to module having a factory node setting of 63 add and configure a module to the online DeviceNet network one a time Record the node address for e...

Страница 32: ...ications Auxilliary web page navigate to Scan List Configuration Node Commissioning 2 Select the device where node address needs to be assigned Once selected the Current Settings aand New Settings are...

Страница 33: ...click the Apply button 5 The following window will appear confirming a successful node address value change Click OK 6 Verify the node address was changed to the desired value in the New settings are...

Страница 34: ...list The EtherNet IP Communicatins Auxilliary provide two methods to configure the scan list Simple and User Defined Simple 1 From the EtherNet IP Communications Auxilliary web page navigate to Scan...

Страница 35: ...on the network the user can select up to six DeviceNet devices to scan Follow the steps below to select specific DeviceNet devices for the scan list 1 From the Ethernet IP Communications Auxilliary w...

Страница 36: ...July 2011 Chapter 4 3 Click on the button to move the selected device into the Scan List 4 Repeat steps 2 and 3 to add five additional DeviceNet devices 5 Click Save at the bottom right of the screen...

Страница 37: ...ry is able to view and configure parameters for a DeviceNet device that supports the full implementation of the Parameter Object Users can utilize the web interface to view and edit parameters for a D...

Страница 38: ...ublication 193 UM014A EN P July 2011 Chapter 5 2 Click on the Identity folder The Identity tab will appear providing information about the selected device 3 Click on the Parameter folder Subfields for...

Страница 39: ...rameters are available select the page number or use the navigation arrows to view the additional parameter screens 5 Select a parameter group that contains programmable parameters then click the Edit...

Страница 40: ...thout an arrow to adjust the values 7 Click Apply once all parameter edits have been completed The Ethernet IP Communications Auxilliary wil download the new parameter values to the device A confirmat...

Страница 41: ...placed With ADR there is no need for software tools to get a replacement device configured and online The Ethernet IP Communications Auxilliary automatically configures the replacement device if the d...

Страница 42: ...checked in the electronic keying field If the new module does not match the criteria of one of the checked boxes the ADR will not function and an ADR error will appear 3 Once the scan list and Device...

Страница 43: ...If the electronic keys for the device at a given node address do not match the saved electronic keys for that node address no ADR download will take place an I O connection will not be allocated and a...

Страница 44: ...c key is detected on node 63 the EtherNet IP Communications Auxilliary will attempt to change the module s network node address to that of the missing scan list node number When successful the EtherNe...

Страница 45: ...t messages have a lower priority compared to I O messages and are used to read and write non critical data I O Messaging RS Logix 5000 software is used to configure I O messaging between an automation...

Страница 46: ...tomation Controller Communications 2 Select the controller type chassis type slot number and project path Then enter a name for the controller and click the OK button 3 Right click the I O Configurati...

Страница 47: ...Chapter 7 4 Select the desired EtherNet IP scanner module then click OK 5 Enter the desired communication settings then click Finish EtherNet IP Network Configuration with Add On Profiles After the co...

Страница 48: ...Controller Communications 1 Place the program in offline mode 2 Right click on the EtherNet IP scanner within the I O Configuration folder then select New Module to open the Select Module Type window...

Страница 49: ...can be used to read and write data from DeviceNet modules being scanned by the EtherNet IP Communications Auxilliary 5 Enter the IP address of the EtherNet IP Communications Auxilliary 6 Select Chang...

Страница 50: ...RSLogix 5000 create the predefined tags The EtherNet IP Communications Auxilliary will now show as a module in the I O Configuration folder Accessing Module Data with Add On Profiles With both the Log...

Страница 51: ...the scanned device use the output tags For diagnostic informaton from the device use the input tags ControlLogix Generic Configuration An existing project can be used or a new project can be created t...

Страница 52: ...UM014A EN_P July 2011 Chapter 7 Automation Controller Communications 3 Right click the I O Configuration folder then select New Module The Select Module Type window will appear 4 Select the desired Et...

Страница 53: ...n click Finish Ethernet IP Communicatoins Auxilliary Once the Logix controller has been configured the EtherNet IP Communications Auxilliary must be added to the I O configuration 1 Place the program...

Страница 54: ...oller Communications 3 Select Generic Ethernet Module then click OK 4 Enter a name for the EtherNet IP Communications Auxiliary The name will create a tag in RSLogix 5000 that can be used to read and...

Страница 55: ...erNet IP Communications Auxilliary as a field of 16 bit values 6 Set the Connection Parameters I O data is accessed using Input Instance 101 and Output Instance 100 The size of the input connection an...

Страница 56: ...time between each scan of the module The recommended RPI time is 250 millisconds Ensure the Inhibit Module is not checked 9 Click OK to add the EtherNet IP Communications Auxilliary to the I O Configu...

Страница 57: ...utomation Publication 193 UM014A EN_P July 2011 57 Automation Controller Communications Chapter 7 2 Select the desired communication path then click the Set Project Path button 3 Select Communications...

Страница 58: ...guration to the PLC Accessing Generic Module Data With both the ControlLogix controller and the EtherNet IP network configured the ControlLogix controller can exchange data with the EtherNet IP Commun...

Страница 59: ...nostic information from the scanned device use the input tags Logic Explicit Messaging CompactLogix ControlLogix and SoftLogix controllers can read and write specific information to and from DeviceNet...

Страница 60: ...integer representing the following information Number of Attributes First Attribute Number Being Returned First Attribute Number Data Status First Attribute Data Last Attribute Number Being Returned...

Страница 61: ...x375 hex Instance 1 dec Attribute 0x00 nex Source Element MSG_Read_Request 0 Source Length 14 bytes Destination MSG_Read_Data 3 Set up the communications path in the Communications tab to read the dat...

Страница 62: ...on 193 UM014A EN_P July 2011 Chapter 7 Automation Controller Communications 4 Click OK When finished the MSG instruction wil lread the 25 parameters from the E3 Overload Relay and place the results in...

Страница 63: ...in the e mail message wil be created from the type of trip or warning that is detected device name device description device location and contact information Fault Conditions for the DeviceNet Scan Li...

Страница 64: ...gured and notifications must be selected Follow these steps to configure an e mail notification 1 In the web browser enter the IP address of the Ethernet IP Communications Auxilliary in the address ba...

Страница 65: ...dentity populate the notification e mail subject and e mail body To configure the Device Identity perform the following steps 1 Select Administrative Settings Device Identity NOTE If desired a passwor...

Страница 66: ...e service provider and looks similar to the example formats below Device Name The name of the Ethernet IP Communications Auxilliary Device Description The description of the Ethernet IP Communications...

Страница 67: ...ggered If two events occur at the same time an e mail will only be sent for the most significant error If the device has been configured to send an e mail for a lower prioritized event and this event...

Страница 68: ...68 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 8 E mail Text...

Страница 69: ...ers are listed below Table 7 Parameter 1 Scanner Status 1 Scanner Status 8 SL Entry Size 2 SL Entry 1 Status 9 Device Keys 3 SL Entry 2 Status 10 Scanlist Config 4 SL Entry 3 Status 11 ADR Record 5 SL...

Страница 70: ...imeout Description Access Rule Data Type Units Value Min Max Default Provides the status of the second scan list entry in the DeviceNet scanner Get WORD 0 2047 0 Bit 0 On Line 4 No Such Device 8 Devic...

Страница 71: ...Timeout Description Access Rule Data Type Units Value Min Max Default Provides the status of the fifth scan list entry in the DeviceNet scanner Get WORD 0 2047 0 Bit 0 On Line 4 No Such Device 8 Devi...

Страница 72: ...mines how electronic keying will be performed Get Set USIN T 0 63 7 Bit 0 Device Type 2 Product Code 4 Minor Revision 1 Vendor 3 Major Revision 5 Minor of Higher Description Access Rule Data Type Unit...

Страница 73: ...Description Access Rule Data Type Units Value Min Max Default Defines the requested packet interval rate in milliseconds used on DeviceNet Polled I O messaging Get Set WORD ms 2 1000 75 Description Ac...

Страница 74: ...74 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 9 Device Parameters...

Страница 75: ...eafety of maintenance personnel as well as others who may be exposed to electrical hazards assicated with maintenance activities follow local safety related work practices e g the NFPS 70W Part II Ele...

Страница 76: ...uminated state 2 The EtherNet IP Communications Auxilliary will perform a duplicate IP address check to verify that another module is not assigned to the same IP address If a duplicate IP address is d...

Страница 77: ...cations Auxilliary will operate as a slave device to a master device on an EtherNet IP network in Run Mode The EtherNet IP NS LED will flash green if there are no network connections established with...

Страница 78: ...tus LED Color State Possible Cause Corrective Action EtherNet IP Network Status NS None The EtherNet IP Communications Auxilliary is not receiving power Check the DeviceNet cable connections and verif...

Страница 79: ...xilliary is not receiving power Check the DeviceNet cable connections and verify that 24V DC exists between the red and black terminals Green Red Not Illuminated Flashing once Normal This is a normal...

Страница 80: ...80 Rockwell Automation Publication 193 UM014A EN P July 2011 Chapter 10 Troubleshooting...

Страница 81: ...Storage Operating Open Enclosed 40 85 C 40 185 F 20 60 C 4 140 F 20 40 C 4 104 F Humidity Operating Damp Heat Steady State Damp Heat Cyclic 5 95 non condensing per IEC 68 2 3 per IEC 68 2 30 Cooling...

Страница 82: ...performance Environment 2 Heavy Industrial WARNING This is a class A product In domestic environment this product may cause radio interference in which case the user may be required to take adequate m...

Страница 83: ...IP Communications Auxiliary is available from the Internet at www ab com networks eds index html It can also be obtained from the EtherNet IP Communications Auxiliary s internal web page CommonIndustr...

Страница 84: ...UINT 0x0001 2 Get Max Instance UINT 0x00011 Attribute ID Access Rule Name Data Type Value 1 Get Vendor ID UINT 2 Get Device Type UINT 12 3 Get Product Code UINT 220 for 193 DNENCAT 221 for 193 DNENCA...

Страница 85: ...lowing class attributes are supported for the Assembly Object Table 29 Assembly Object Class Attributes Instance Attributes Instances Connection points implements the following data attributes Attribu...

Страница 86: ...to the sixth scan list entry Byte Size Contents 4 Bytes Logix Status Word 2 Bytes DeviceNet Scanner Status Parameter 1 2 Bytes Scan List Entry 1 Status Word Parameter 2 2 Bytes Scan List Entry 2 Statu...

Страница 87: ...Contents 2 Bytes ScanList I O Size 2 Bytes Data Link Update Interval ms 1 Byte Data Link 1 Node 2 Bytes Data Link 1 Parameter 1 Byte Data Link 2 Node 2 Bytes Data Link 2 Parameter 1 Byte Data Link 3...

Страница 88: ...ue 1 Get Revision UINT 0x0001 2 Get Max Instance UINT 0x0029 8 Get Parameter Class Descriptor WORD 0x000B Attribute ID Access Rule Name Data Type Value 1 Get Set Value Specified in Descriptor N A 2 Ge...

Страница 89: ...T 21 Get Decimal Precision USINT Parameter Dependent Service Code Implemented for Service Name Class Instance 0x01 No Yes Get Attribute All 0x0E Yes Yes Get Attribute Single 0x10 No Yes Set Attribute...

Страница 90: ...bject will be supported Table 44 Non Volatile Storage Object Instances Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 1 Attribute ID Access Rule Name Data Type Value 1 Set 802 1Q Ta...

Страница 91: ...nstance UINT 2 3 Get Num Instances UINT 2 8 Get Entry Port UINT 1 9 Get Port Instance Info Array of Structure of 1 Port Type UINT Port Number UINT Attribute ID Access Rule Name Data Type Value 1 Get P...

Страница 92: ...ue 1 Get Status DWORD 2 Get Configuration Capability DWORD 0x00000014 3 Get Set Configuration Control DWORD 0 Configuration from NVS 2 Configuration from DHCP 4 Get Physical Link Object Struct of UINT...

Страница 93: ...x10 No Yes Set_Attribute_Single Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 1 Attribute ID Access Rule Name Data Type Value 1 Get Interface Speed UDINT 10 or 100 Mbit sec 2 Get I...

Страница 94: ...ocal distributor a Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem with a hardware module within the first 24 hours...

Страница 95: ...pped from the manufacturing facility However if your product is not functioning and needs to be returned United States Contact your distributor You must provide a Customer Support case number dial 1 4...

Страница 96: ...96 Rockwell Automation Publication 193 UM014A EN P July 2011 Appendix B...

Страница 97: ......

Страница 98: ...24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running New Product Satisfaction Retur...

Отзывы: