Publication 1769-UM002B-EN-P - July 2005
4-6
Module Data, Status, and Channel Configuration for the Output Modules
1769-OF2 Channel Configuration
Both channel configuration words (0 and 1) consist of bit fields, the settings of
which determine how the corresponding channel operates. See the table below
and the descriptions that follow for valid configuration settings and their
meanings.
Table 4.4 1769-OF2 Bit Definitions for Channel Configuration Words 0 and 1
Bit(s)
Define
These bit settings
Indicate this
15
14
13
12
11
10
9
8
7 6 5 4 3
2
1
0
0
Program/Idle to
Fault Enable
Not Used
0
Program Mode Data
Applied
1
Fault Mode Data Applied
1
Reserved
Reserved
2
Program/Idle
Mode
0
Program Mode Hold Last
State
1
Program Mode
User-Defined Value
3
Fault Mode
0
Fault Mode Hold Last
State
1
Fault Mode User-Defined
Value
4-7
Reserved
Reserved
(1)
8-11
Output
Type/Range Select
0
0
0
0
-10V dc to +10V dc
0
0
0
1
0 to 5V dc
0
0
1
0
0 to 10V dc
0
0
1
1
4 to 20 mA
0
1
0
0
1 to 5V dc
0
1
0
1
0 to 20 mA
Not Used
(2)
12-14
Output Data
Format Select
0
0
0
Raw/Proportional Data
0
0
1
Engineering Units
0
1
0
Scaled-for-PID
(3)
0
1
1
Percent Range
Not Used
15
Enable Channel
1
Enabled
0
Disabled
(1)
If reserved bits are not equal to zero, a configuration error occurs.
(2)
Any attempt to write a non-valid (not used) bit configuration into any selection field results in a module configuration error. See Configuration Errors on page 5-6.
(3)
This range is applicable to the PID function of the MicroLogix 1500 packaged controller, PLC, or SLC controllers. Logix controllers can use this or one of the other ranges for
their PID functions.
Содержание Allen-Bradley 1769-IF4
Страница 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Страница 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Страница 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Страница 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Страница 118: ...Publication 1769 UM002B EN P July 2005 4 36 Module Data Status and Channel Configuration for the Output Modules Notes ...
Страница 151: ...Publication 1769 UM002B EN P July 2005 Module Addressing and Configuration with MicroLogix 1500 B 9 ...
Страница 152: ...Publication 1769 UM002B EN P July 2005 B 10 Module Addressing and Configuration with MicroLogix 1500 Notes ...
Страница 183: ......