Publication 1769-UM002B-EN-P - July 2005
2-6
Installation and Wiring
6.
To allow communication between the controller and module, move the
bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in
place.
7.
Attach an end cap terminator (5) to the last module in the system by
using the tongue-and-groove slots as before.
8.
Lock the end cap bus terminator (6).
Mounting
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc.
Allow 50 mm (2 in.) of space on all sides for adequate ventilation.
Figure 2.2 Space Requirements
ATTENTION
When attaching I/O modules, it is very important
that the bus connectors are securely locked together
to ensure proper electrical connection.
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be
used to terminate the end of the bus.
ATTENTION
During panel or DIN rail mounting of all devices, be sure
that all debris (metal chips, wire strands, etc.) is kept from
falling into the module. Debris that falls into the module
could cause damage at power up.
Host Controller
Compact I/
O
Compact I/
O
Compact I/
O
Compact I/
O
Compact I/
O
En
d Cap
Side
Side
Top
Bottom
Содержание Allen-Bradley 1769-IF4
Страница 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Страница 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Страница 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Страница 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Страница 118: ...Publication 1769 UM002B EN P July 2005 4 36 Module Data Status and Channel Configuration for the Output Modules Notes ...
Страница 151: ...Publication 1769 UM002B EN P July 2005 Module Addressing and Configuration with MicroLogix 1500 B 9 ...
Страница 152: ...Publication 1769 UM002B EN P July 2005 B 10 Module Addressing and Configuration with MicroLogix 1500 Notes ...
Страница 183: ......