Publication 1769-UM002B-EN-P - July 2005
A-8
Specifications
Output Error Over Full
Temperature Range
(0 to 60°C [32 to +140°F])
Voltage: ±0.8%
Current: ±0.55%
Output Offset Error
(0 to 60°C [32 to +140°F])
±0.05%
Output Impedance
15
Ω
(typical)
Open and Short-Circuit
Protection
Yes
Maximum Short-Circuit Current
21 mA
Output Overvoltage Protection
Yes
Time to Detect Open Wire
Condition (Current Mode)
10 ms typical
13.5 ms maximum
Output Response at Power Up
and Power Down
±0.5 V spike for <5 ms
Rated Working Voltage
(6)
30V ac/30V dc
Module OK LED
On: module has power, has passed internal
diagnostics, and is communicating over the bus.
Off: Any of the above is not true.
Channel Diagnostics
Over or under range by bit reporting
output wire broken or load resistance high by bit
reporting (current mode only)
Output Group to Backplane
Isolation
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced
insulation)
Vendor I.D. Code
1
Product Type Code
10
Product Code
32
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The
module will continue to convert the analog input up to the maximum full scale range. The flag automatically
resets when within the normal operating range.
(2)
Step response is the period of time between when the D/A converter was instructed to go from minimum to full
range until the device is at 63% of full range. Time applies to one or both channels.
(3)
Includes offset, gain, non-linearity and repeatability error terms.
(4)
Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.
(5)
Repeatability is the ability of the output module to reproduce output readings when the same controller value is
applied to it consecutively, under the same conditions and in the same direction.
(6)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the
input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc
potential above ground).
(7)
If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.
Specification
1769-OF2 (Series B and later)
Содержание Allen-Bradley 1769-IF4
Страница 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Страница 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Страница 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Страница 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Страница 118: ...Publication 1769 UM002B EN P July 2005 4 36 Module Data Status and Channel Configuration for the Output Modules Notes ...
Страница 151: ...Publication 1769 UM002B EN P July 2005 Module Addressing and Configuration with MicroLogix 1500 B 9 ...
Страница 152: ...Publication 1769 UM002B EN P July 2005 B 10 Module Addressing and Configuration with MicroLogix 1500 Notes ...
Страница 183: ......