16
Rockwell Automation Publication 1606-RM002A-EN-P - March 2019
Power Supply - 24V, 10 A, 240 W, Three-phase Input
EMC
EMC Immunity
According to Generic Standards EN 61000-6-1 and EN 61000-6-2
Criterion
(1)
(1) Criterion A: Power supply shows normal operation behavior within the defined limits.
Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the
power supply occurs.
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8 kV
15 kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz-2.7 GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
4 kV
2 kV
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L1 ->L2, L2 ->L3, L1 ->L3,
L1/L2/L3->PE
2 kV
4 kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+ ->-
+/- ->PE
500V
1 kV
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0.15…80 M Hz
10V
Criterion A
Mains voltage dips (Dips
on 3 phases)
EN 61000-4-11
0% of 380V AC
0% of 480V AC
0V AC, 20 ms
0V AC, 20 ms
Criterion A
Criterion A
Mains voltage dips (Dips
on 2 phases)
EN 61000-4-11
40% of 380V AC
40% of 480V AC
70% of 380V AC
70% of 480V AC
200 ms
200 ms
500 ms
500 ms
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11
–
5 s
Criterion C
Powerful transients
VDE 0160
Over entire load range
1550V, 1.3 ms
Criterion A
EMC Emission
According to Generic Standards: EN 61000-6-3, EN 610000-6-4
Conducted emission input lines
EN 55011, EN 55022
FCC Part 15
CISPR 11, CISPR 22
Class B
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Fulfilled for class A equipment
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled
(1)
(1) Tested with constant current loads, non-pulsing.
This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device cannot
cause harmful interference, and (2) this device must accept any interference received, including interference that can
cause undesired operation.
Switching Frequency
Description
Main converter
60k Hz…140k Hz
Output load and input voltage dependent