14
Rockwell Automation Publication 1606-RM002A-EN-P - March 2019
Power Supply - 24V, 10 A, 240 W, Three-phase Input
Connection Terminals
The terminals are IP20 finger safe constructed and suitable for field and factory
wiring.
Daisy Chaining
Daisy chaining (jumping from one power supply output to the next) is allowed as
long as the average output current through one terminal pin does not exceed
25 A. If the current is higher, use a separate distribution terminal block. See
Attribute
Input and Output
Type
Screw termination
Solid wire
Max 6 mm
2
Stranded wire
Max 4 mm
2
American wire gauge
AWG 20…10
Wire diameter, max (including
ferrules)
2.8 mm (0.11 in.)
Tightening torque, recommended
1 Nm, 9 lb-in
Wiring stripping length
7 mm (0.28 in.)
Screwdriver
3.5 mm slotted or Phillips no. 1
Figure 15 - Daisy Chaining of Outputs
Figure 16 - Using Distribution Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25A!
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Содержание Allen-Bradley 1606-XLE240E-3