1397 Inverting Fault Circuit Breaker

7

1397-5.29     September, 1998

Drive

M

A1

Motor A1

M

Motor
Armature

Removable Link
  Removed

Motor A2

Motor S1

Motor S2

Series Field

Customer supplied wire
Size to same gauge
as DB kit leads.

DRV

S2

MOT

A2

A2/S1

Inverting Fault Breaker
     Aux Contact

1 > Any other customer interlocks
      must be connected in series
     to terminals 9 and 11

1 > To Regulator board
      terminals 9 & 11

M

Disconnect
existing A2
at Power I/F
PC board

To Power I/F
PC board A2

Figure 5.
Inverting Fault Circuit Breaker
with a Series Field and Dynamic Braking

Wiring

If you are using the Inverting Fault Circuit Breaker with a Series 
Field (S1 to A2) and Dynamic Braking:

1

Refer to Figure 7.  Remove the removable link (bus section 
connected to drive output terminal A2/S1) by removing the four 
nuts and bolts that hold it in place.  You may need to dismount 
the drive in order to gain access to the removable link.  If so, 
re-mount the drive after the link has been removed.

2

Refer to Figure 5.  Connect motor series field lead S2 to Inverting 
Fault Circuit Breaker terminal MOT.  (See Figure 9 for the 
location of the breaker’s MOT terminal.)  Terminate the breaker 
side of the leads with lugs of the appropriate gauge.

3

Using wire of the same gauge as the motor leads, connect 
Inverting Fault Circuit Breaker terminal DRV to drive output 
terminal S2.  (See Figure 9 for the location of the breaker’s DRV 
terminal.)  Terminate the breaker side of the wires with lugs of 
the appropriate gauge.

4

Using wire the same gauge as the DB kit leads, connect motor 
armature lead A1 to drive terminal A1.

Proceed to "Wire Assembly Connections".

4

Using wire the same gauge as the DB kit leads, connect motor 
armature lead A1 to drive terminal A1.

5

Connect motor armature lead A1 to drive terminal A1.

Содержание Allen-Bradley 1397

Страница 1: ...lly occurs as a result of loss of AC line If this happens the AC input transformer becomes a short circuit across the motor Since the SCRs in the bridge no longer turn off the motor s stored mechanical energy is regenerated into the short circuit The inverting Fault Circuit Breaker interrupts the generator action protecting the SCR bridge and the motor The Inverting Fault Circuit Breaker is a magn...

Страница 2: ... the Inverting Fault Circuit Breaker switch is in the OFF position 2 Choose an appropriate location for mounting the Inverting FaultCircuitBreaker Notethatwireassembliesshippedwith the kit are 152 4 cm 60 inches in length 4 Mount the Inverting Fault Circuit Breaker as follows a Drive the top two 2 M6 self tapping screws half way into the holes drilled in Step 3 b LifttheInvertingFaultCircuitBreake...

Страница 3: ...l MOT Refer to Figure 9 for the location of the breakers s MOT terminal Terminate the breaker side of the leads with lugs of the appropriate gauge Wiring The method used to wire the Inverting Fault Circuit Breaker depends on whether the drive is equipped with dynamic braking and or a motor series field Choose the appropriate wiring procedure for your application from the following procedures If yo...

Страница 4: ... From Field Supply RRB1 5 RRB1 6 14 13 M AUX Field DB TB 35 F2 37 F1 F2 F1 4 3 2 P6 2 DBCR Jumper Must be installed except for Special Apps P6 5 Not used on standard DB application Used only for special applications 1 To regulator terminals 9 11 1 Any other customer interlocks must be connected in series to terminals 9 and 11 2 Usingwireof thesamegaugeasthemotorleads connect Inverting Fault Circui...

Страница 5: ...ount the drive in order to gain access to the removable link If so re mount the drive after the link has been removed Wiring If you are using the Inverting Fault Circuit Breaker with Dynamic Braking 2 Refer to Figure 3 Connect motor armature lead A2 to Inverting Fault Circuit Breaker terminal MOT See Figure 9 for the location of the breakers MOT terminal Terminate the breaker side of the leads wit...

Страница 6: ...s Field S1 to A2 Wiring 1 Refer to Figure 4 Connect motor series field lead S2 to Inverting Fault Circuit Breaker terminal MOT See Figure 9 for location of the breaker s MOT terminal Terminate the breaker side of the leads with lugs of the appropriate gauge If you are using the Inverting Fault Circuit Breaker with a Series Field S1 to A2 2 Using wire the same gauge as the motor leads connect Inver...

Страница 7: ...four nuts and bolts that hold it in place You may need to dismount the drive in order to gain access to the removable link If so re mount the drive after the link has been removed 2 Refer to Figure 5 Connect motor series field lead S2 to Inverting Fault Circuit Breaker terminal MOT See Figure 9 for the location of the breaker s MOT terminal Terminate the breaker side of the leads with lugs of the ...

Страница 8: ...ts and bolts that hold it in place You may need to dismount the drive in order to gain access to the removable link If so re mount the drive after the link has been removed 2 Refer to Figure 6 Connect motor series field lead S2 to Inverting Fault Circuit Breaker terminal MOT See Figure 9 for the location of the breaker s MOT terminal Terminate the breaker side of the leads with lugs of the appropr...

Страница 9: ... Route this wire to Inverting Fault Circuit Breaker terminal MOT Cut the wire to length as required and terminatetheend withthering lugsuppliedinthekit 4 Connect the ring lug to terminal MOT of the Inverting Fault Circuit Breaker as shown in Figure 9 5 Connect the spade connectors of the twisted pair harness to the male connectors on the yellow lead and the blue yellow striped lead coming out of t...

Страница 10: ...Fault Circuit Breaker 10 1397 5 29 September 1998 Remove existing A2 connection DBR A2 S1 Enfld 1 A2 A1 Line 1 Line 2 Line 3 DBR A2 S1 Remove Screws A1 S2 A1 S2 Figure 8 Power Interface Board and Terminal A2 Locations ...

Страница 11: ...A2 FDBK to Power I F Board Shield Top and Bottom 2 Places M6 x 12 mm Self Tapping Screw 6 Places To Regulator Board Terminal Block MOT DRV A2 FDBK TOP VIEW SIDE VIEW BOTTOM VIEW 1 2 Ring Lug M5 x 16 mm Self Tapping Screw 8 Places Figure 10 Control Terminal Strip 10 8 9 11 12 13 14 User Contacts Inverting Fault Circuit Breaker ...

Страница 12: ...llowing sequence a RefertoFigure9andloosenthe 8 M5x16mmscrewsinthefaceof the Assembly Base Plate b Insert the shield keyholes onto the screws and slide each shield into place c Tighten the screws to hold the shields in place Do not overtighten 4 Set the Inverting Fault Circuit Breaker to the ON position 5 Remove the lockout and tag and reconnect power to the drive 6 Turn on power to the drive and ...

Страница 13: ...1397 5 29 September 1998 This Page Intentionally Blank ...

Страница 14: ...1397 5 29 September 1998 This Page Intentionally Blank ...

Страница 15: ...Publication 1397 5 29 September 1998 P N 191100 02 Supersedes July 1998 Copyright 1995 Rockwell International Corporation All rights reserved Printed in USA ...

Отзывы: