28
Publication 6186M-UM001J-EN-P - July 2008
Chapter 2
Installing the Monitor
Connecting dc Power
The 1200M, 1500M, 1700M, and 1900M monitors connect to a dc
power source using a dc input terminal block.
Follow these steps to connect power to the monitor.
1.
Turn off the main power switch or breaker.
2.
Route the power wires from your dc power supply and connect
the leads to the dc input terminal block on the monitor.
The monitors accept a 9…36V dc input power-supply
connection.
3.
Tighten the screw terminals to provide a good connection.
4.
Secure the terminal block connector to the unit by using the two
side screws.
5.
Restore dc power.
ATTENTION
Connect the product to earth ground using a 1.31 mm
2
(16 AWG) or larger external wire. The ground wire should have
green insulation with a yellow stripe for easy identification.
+9V…+36V
Gnd